AK-CC55 Multi Coil
7.
Set the desired cut-out temperature r00
8.
Select refrigerant via parameter o30
9.
Set the pressure transmitter min. and max. range via parameter o20 and o21
10.
Set the desired defrost method in d01
11.
Set the interval time between defrost starts in d03
12.
Set the desired defrost sensor in d10
13.
Set the maximum defrost time in d04
14.
Set the defrost stop temperature in d02
15.
Open parameter r12 and start the regulation
16.
Go through the parameter list and change the factory values where needed
17.
Get the controller up and running on network:
◦ MODBUS: Activate scan function in system unit
◦ If another data communication card is used in the controller:
▪ Lon RS485: Activate the function o04
▪ Ethernet: Use the MAC address
Table 13: Food type settings
Setting of presettings (r89).
After setting 1-5, setting is returned to 0.
Food type
Temperature (r00)
Max. temp. setting (r02)
Min. temp. setting (r03)
Upper alarm limit (A13)
Lower alarm limit (A14)
Can only be set when r12=0.
© Danfoss | Climate Solutions | 2022.08
1
2
Vegetables
Milk
8 °C
0 °C
10 °C
4 °C
4 °C
-4 °C
14 °C
8 °C
0 °C
-5 °C
3
4
Meat/fish
Frozen food
-2 °C
-20 °C
2 °C
-16 °C
-6 °C
-24 °C
8 °C
-15 °C
-5 °C
-30 °C
BC365022028193en-000201 | 32
5
Ice cream
-24 °C
-20 °C
-28 °C
-15 °C
-30 °C