AK-CC55 Multi Coil
Function
Values
Refrigerant
0=Not seleted, 6=R13, 7=R13b1, 2=R22,
8=R23, 14=R32, 11=R114, 3=R134a,
12=R142b, 24=R170, 15=R227,
25=R290, 16=R401A, 18=R402A,
19=R404A, 21=R407A, 22=R407B,
20=R407C, 37=R407F, 49=R407H,
23=R410A, 32=R413A, 30=R417A,
31=R422A, 33=R422D, 34=R427A,
35=R438A, 40=R448A, 41=R449A,
48=R449B, 43=R450A, 44=R452B,
45=R454B, 9=R500, 4=R502, 10=R503,
17=R507, 36=R513A, 26=R600,
27=R600a, 5=R717, 28=R744,
46=R1233zdE, 38=R1234ze,
39=R1234yf, 47=R1234zeZ, 29=R1270,
42=R452A, 1=User defined display,
13=User defined
DI2 Configuration
0=None, 1=DI status, 2=Door function,
3=Door alarm, 4=Defrost start, 5=Main
switch, 6=Night setback, 7=Thermostat
band, 8=Alarm at closed, 9=Alarm at
open, 10=Case cleaning, 11=Forced
cooling, 13=Coordinated defrost,
14=Forced closing, 15=Shutdown,
16=Light control, 20=Leak detection,
21=Adaptive liquid control, 29=Door
fan stop
Light control mode
1=Day and night, 2=Network, 3=Door
switch, 4=Network (Fallback), 5=Digital
input
MC Light signal
0=OFF, 1=ON
Rail heat ON cycle day
Rail heat ON cycle night
Rail heat period time
Case cleaning mode
0=OFF, 1=Fans run, 2=Cleaning
Application mode
1=1. One evaporator MT/LT, 2=2. Two
evaporators MT/LT, 3=3. Three evapora-
tors MT, 4=4. Coldroom 2 MT/HT, 5=5.
Coldroom 2 MT/LT
Access code 2
Make new factory
0=OFF, 1=ON
DI3 Configuration
0=None, 1=DI status, 2=Door function,
3=Door alarm, 4=Defrost start, 5=Main
switch, 6=Night setback, 7=Thermostat
band, 8=Alarm at closed, 9=Alarm at
open, 10=Case cleaning, 11=Forced
cooling, 13=Coordinated defrost,
14=Forced closing, 15=Shutdown,
16=Light control, 20=Leak detection,
21=Adaptive liquid control, 29=Door
fan stop
Rail heat control mode
0=ON, 1=Day/Night timer, 2=Dewpoint
ctrl.
Dewpoint min. limit
Dewpoint max. limit
Rail heat min. ON cycle
Door restart inj. delay
Fan at forced closing
0=OFF, 1=ON, 2=OFF and suppress de-
frost, 3=ON and suppress defrost
Display readout
1=Ther. air A, 2=Average all, 3=Maxi-
mum all, 4=S4A and S4B
Light at Main switch OFF 0=OFF, 1=Normal ctrl.
(1)
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
© Danfoss | Climate Solutions | 2022.08
R-W
Code
1
2
3
1-3
(1)
o30
*
*
*
1-2
o37
*
*
*
(1)
1-2
o38
*
*
*
1-2
o39
*
*
*
1-2
o41
*
*
*
1-2
o42
*
*
*
1-2
o43
*
*
*
0-1
o46
*
*
*
1-3
o61
*
*
*
(1)
2-2
o64
*
*
*
3-3
o67
*
*
*
(1)
1-2
(1)
o84
*
*
*
1-2
o85
*
*
*
1-2
o86
*
*
*
1-2
o87
*
*
*
1-2
o88
*
*
*
1-2
o89
*
*
*
1-2
o90
*
*
*
1-2
o97
*
*
*
1-2
o98
*
*
*
4
5
Min. value Max. value Fact. value
*
*
0
49
*
*
0
29
*
*
1
5
*
*
0
1
*
*
0 %
100 %
*
*
0 %
100 %
6 min
60 min
*
*
0
2
*
*
1
5
*
*
0
999
*
*
0
1
*
*
0
29
*
*
0
2
*
*
-10.0 °C
o87
*
*
o86
50.0 °C
*
*
0 %
100 %
*
*
0 min
240 min
*
*
0
3
*
*
1
4
*
*
0
1
BC365022028193en-000201 | 36
0
0
1
0
100%
100%
6min
0
1
0
0
0
0
8.0 °C
17.0 °C
30%
30 min
1
1
0