Defrost; Injection Control; Fan Control; Defrost Schedule - Danfoss AK-CC55 Multi Coil User Manual

Case/room controller (eev)
Hide thumbs Also See for AK-CC55 Multi Coil:
Table of Contents

Advertisement

AK-CC55 Multi Coil

Defrost

Table 16: Defrost
Function
Values
0=None, 1=Electrical, 4=Air/
Defrost method
Offcycle
Defrost stop limit A
Defrost start interval
Max. defrost time
Time staggering power-up
Drip off time
Fan start delay
Fan start temperature
0=OFF, 1=ON, 2=OFF at drip,
Fan control during defrost
3=OFF at high temp
0=Time, 1=S5 sensor, 2=S4 sen-
Defrost stop method
sor
Pump down delay
Max. thermostat run time
Min. defrost time
Rail heat during defrost
0=OFF, 1=ON, 2=Normal control
Defrost stop limit 2
Max. defrost time 2
Display delay after defrost
Fan stop temperature

Injection control

Table 17: Injection control
Function
Values
Max. superheat limit
Min. superheat limit
MOP temperature
AKV Period time
(1)
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.

Fan control

Table 18: Fan control
Function
Values
Fan stop high S5 temp.
0=No pulsing, 1=Pulsing cut-
Fan pulsing mode
out, 2=Pulsing cut-out night
Fan period time
Fan ON cycle

Defrost schedule

Table 19: Defrost schedule
Function
Values
Defrost schedule
0=No, 1=Yes
Def. start 1 - Hours
Def. start 1 - min
Def. start 2 - Hours
Def. start 2 - min
Def. start 3 - Hours
Def. start 3 - min
Def. start 4 - Hours
Def. start 4 - min
Def. start 5 - Hours
© Danfoss | Climate Solutions | 2022.08
R-W
Code
1
2
3
1-3
d01
*
*
*
1-2
d02
*
*
*
1-2
d03
*
*
*
1-2
d04
*
*
*
1-2
d05
*
*
*
1-2
d06
*
*
*
1-2
d07
*
*
*
1-2
d08
*
*
1-2
d09
*
*
*
1-2
d10
*
*
*
1-2
d16
*
*
*
1-2
d18
*
*
*
1-2
d24
*
*
*
1-2
d27
*
*
*
1-2
d28
*
*
*
1-2
d29
*
*
*
1-2
d40
*
*
*
1-2
d41
*
*
*
R-W
Code
1
2
3
1-2
n09
*
*
*
1-2
n10
*
*
*
1-2
n11
*
*
*
1-2
n13
*
*
*
(1)
R-W
Code
1
2
3
1-2
F04
*
*
1-2
F05
*
*
*
1-2
F06
*
*
*
1-2
F07
*
*
*
R-W
Code
1
2
3
1-2
t00
*
*
*
1-2
t01
*
*
*
1-2
t11
*
*
*
1-2
t02
*
*
*
1-2
t12
*
*
*
1-2
t03
*
*
*
1-2
t13
*
*
*
1-2
t04
*
*
*
1-2
t14
*
*
*
1-2
t05
*
*
*
4
5
Min.value
Max.value
*
*
0
4
*
*
0.0 °C
50.0 °C
*
*
0 hours
240 hours
*
*
0 min
360 min
*
*
0 min
240 min
*
*
0 min
60 min
*
*
0 min
60 min
*
-60.0 °C
10.0 °C
*
*
0
3
*
*
0
2
*
*
0 min
60 min
*
*
0 hours
240 hours
*
*
0 min
d04
*
*
0
2
*
*
0.0 °C
50.0 °C
*
*
0 min
360 min
*
*
5 min
240 min
*
*
-20.0 °C
20.0 °C
4
5
Min. value Max. value Fact. value
*
*
n10
20.0 °C
*
*
2.0 °C
n09
*
*
-60.0 °C
15.0 °C
*
*
3 s
6 s
4
5
Min. value Max. value Fact. value
*
-60.0 °C
50.0 °C
*
*
0
2
*
*
1 min
30 min
*
*
0 %
100 %
4
5
Min. value Max. value Fact. value
*
*
0
1
*
*
0 hours
23 hours
*
*
0 min
59 min
*
*
0 hours
23 hours
*
*
0 min
59 min
*
*
0 hours
23 hours
*
*
0 min
59 min
*
*
0 hours
23 hours
*
*
0 min
59 min
*
*
0 hours
23 hours
BC365022028193en-000201 | 34
Fact.value
1
6.0 °C
8 hours
45 min
0 min
0 min
0 min
5.0 °C
1
0
0 min
0 hours
0 min
1
6.0 °C
45 min
30 min
0.0 °C
12.0 °C
3.0 °C
15.0 °C
6 s
50.0 °C
0
5 min
100%
0
0 hour
0 min
0 hour
0 min
0 hour
0 min
0 hour
0 min
0 hour