Controller Fault Notes - GE PACSystems RXi User Manual

Distributed io controller
Table of Contents

Advertisement

Group/
Error
Code
Description
135-218
Critical over-
temperature failure
135-All
Critical fatal error.
others
137-0
Communications failure
during store
137-1
Communications lost
during run mode store
137-2
Communications lost
during cleanup for run
mode store
137-3
Power lost during a run
mode store
140-1
Events during power-up
through
140-30
140-31
Miscellaneous internal
through
system events
140-52
140-53
Access control fault
140-54
Miscellaneous internal
and
system events
greater

14.4.3 Controller Fault Notes

This section contains additional information about specific faults listed in Section 14.4.2
Controller Fault Descriptions and Corrective Actions.
Error code 11-13, DCD Length Mismatch Fault Extra Data
Byte
[0]
GFK-2816F
CPU's critical operating temperature
exceeded.
A critical fatal error has occurred during
normal Controller operation from which the
Controller cannot recover.
Communications with the programming
device performing the store was interrupted
another failure that terminates the store
occurred. As long as this fault is present in
the system, the controller will not transition to
Run mode. This fault is not automatically
cleared on power-up; you must specifically
clear the condition.
Communications or power was lost during a
Run Mode Store. The new program or block
was not activated and was deleted.
Communications was lost, or power was lost
during the cleanup of old programs or blocks
during a Run Mode Store. The new program
or block is installed, and the remaining
programs and blocks were cleaned up.
Power was lost in the middle of a Run Mode
Store.
Records conditions that may provide useful
information to Technical Support.
Records conditions that may provide useful
information to Technical Support.
If data access is prevented because of the
Enhanced Security settings, the Controller
logs a fault into the fault table. This fault can
be used to help diagnose access problems.
To prevent overflowing the fault table, only
one fault is logged until the fault table is
cleared.
Records non-critical conditions that may
provide useful information to Technical
Support.
Value
FF
Cause
August 2015
Chapter 14. Diagnostics
Recommended Correction
Turn off RXi to allow heat to
disperse and implement
measures to regulate ambient
operating temperature.
Display the controller fault table.
Contact Technical Support and
provide the information
contained in the fault entry.
For details, refer to page 280.
Clear the fault and retry the
download of the program or
configuration file.
Perform the Run Mode Store
again.
None required. This fault is
informational.
Delete and restore the program.
This error is fatal.
No corrective action is required
unless this fault occurs with
other specific faults.
No corrective action is required
unless the fault occurs with
other specific faults.
No corrective action is required
unless this fault occurs with
other specific faults.
Refer to page 281 for additional
information.
This fault is informational.
No corrective action is required
unless this fault occurs with
other specific faults.
279