Chapter 4. Configuration
Storing (Downloading) Hardware Configuration
4.4
A PACSystems control system is configured by creating a configuration file in the
programming software, then transferring (downloading) the file from the programmer to the
controller.
The CPU stores the configuration file in its non-volatile memory. After the configuration is
stored, I/O scanning is enabled or disabled according to the newly stored configuration
parameter, Stop-Mode I/O.
Before you can store the hardware configuration to the RXi Controller, you must first set the
IP address in the Ethernet Interface using the IDM (page 29.)
1. In the programmer software, go to the Project tab of the Navigator, right click the Target,
2. Right click the Target and choose Online Commands, Set Programmer Mode. Make sure
3. Right click the Target node, and choose Download to Controller.
4. In the Download to Controller dialog box, select the items to download and click OK.
Note:
Note:
70
choose Set as Active Target and then Go Online.
the CPU is in Stop mode.
If you download to a PACSystems target that already has a project on it, the existing
project is overwritten.
If hardware configuration and logic are coupled they cannot be stored independently.
They must be stored at the same time.
PACSystems* RXi Distributed IO Controller User Manual
GFK-2816F