Chapter 13. OPC UA Server

Publish RXi Application Variables to OPC UA Address Space

13.5
Machine Edition allows you to select application variables to include in the OPC UA address
space. This is done by means of the variable's publish attribute. The publish attribute is
accessed using the variable Inspector within Machine Edition. The Machine Edition variable
Inspector is displayed in the screenshot below for reference.
The available PME Publish attribute selections are as follows as they apply to the OPC UA
server:
252
Selection
False
Variable is not published to OPC UA Address Space
Internal
Variable is not published to OPC UA Address Space
External
Publish variable to OPC UA address space and allow the OPC
Read/Write
UA client Read and Write Access
External
Publish variable to OPC UA address space and allow the OPC
ReadOnly
UA client Read Access only
The RXi's OPC UA address space supports 12,500 addressable elements. If
Note:
more than 12,500 addressable elements are published, only the first 12,500
(listed alphabetically) will be made available in the OPC UA address space.
Each index of a variable array counts as a unique, addressable element.
PACSystems* RXi Distributed IO Controller User Manual
Machine Edition Variable Inspector
Description – OPC UA Server Specific Usage
GFK-2816F