Chapter 14. Diagnostics
Group/
Error
Code
Description
CPU's critical operating
13-168
temperature exceeded.
13-h
PNC hardware failure.
13-All
CPU hardware failure
others
14-450
LAN interface hardware
through
failure
14-454
14-All
Module hardware failure
others
16-1
Unsupported board type
16-2,
COMMREQ frequency
16-3
too high
16-4
Option module software
through
failure
16-399
16-400
LAN system software
and
fault
higher
276
Cause
The CPU's critical operating temperature
exceeded.
The PNC has encountered a hardware
related failure.
h – Error code that provides more information
about what part of the PNC's hardware had
failure.
For a memory failure in the CPU (one of the
faults reported as a CPU hardware failure),
the address of the failure is stored in the first
four bytes of the Fault Extra Data.
A module hardware failure has been
detected.
The board is not one of the supported types.
COMMREQs are being sent to a module
faster than it can process them.
Software failure detected on an option
module.
The Ethernet interface software has detected
an unusual condition and recorded an event
in its exception log.
The Fault Extra Data contains the
corresponding event in the Ethernet
exception log, which can be viewed by the
Ethernet interface's Station Manager function.
The first two digits of Fault Extra Data contain
the Event type; the remaining data
correspond to the four-digit values for Entry 2
through Entry 6. Some exceptions may also
contain optional multi-byte SCode and other
data.
PACSystems* RXi Distributed IO Controller User Manual
Recommended Correction
Turn off the RXi Controller to
allow heat to disperse and
implement measures to regulate
ambient operating temperature.
Contact Technical Support.
Contact Technical Support.
Contact Technical Support.
Replace the affected module.
Upload the configuration file
and verify that the software
recognizes the board type
in the file. If there is an
error, correct it, download
the corrected configuration
file, and retry.
Display the controller fault.
Contact Technical Support
and provide the information
contained in the fault entry.
Change the application
program to send
COMMREQs to the module
at a slower rate or check
the completion status of
each COMMREQ before
sending the next.
Reload software into the
indicated module.
Replace the module.
For information on interpreting
the fault extra data, refer to the
PACSystems TCP/IP Ethernet
Communications Station
Manager User Manual,
GFK-2225.
GFK-2816F