I/O Fault Details

14.5
The I/O fault table reports the following data about faults:
■ Fault Group
■ Fault Action
■ Fault category
■ Fault type
■ Fault description
All faults have a fault category, but a fault type and fault group may not be listed for every
fault. To view the detailed information pertaining to a fault, click the fault entry in the I/O Fault
Table.
An I/O fault table entry contains up to 21 bytes of I/O fault extra data that contains additional
information related to the fault. Not all entries contain I/O fault extra data.
Note:

14.5.1 I/O Fault Groups

Group Number
16
The fault action indicated is not applicable if the fault is displayed as informational. Faults displayed
as informational, always behave as informational.
17
The fault action for the IOC Software Failure group 15 always matches the action used by the Loss of
or Missing IOC group 2. If the Loss of or Missing IOC group is configured, the IOC Software Failure
group is also configured to take the same fault action.
GFK-2816F
The model number mismatch and I/O type mismatch faults are reported in the
controller fault table under the System Configuration Mismatch group. They are not
reported in the I/O fault table.
Group Name
2
Loss of or Missing IOC
3
Loss of or Missing I/O module or
network Device
6
Addition or Reset of, or Extra IOC
7
Addition of or Extra I/O module or
network Device
9
IOC or I/O Bus Fault
10
I/O Module Fault
15
IOC Software Failure
16
Module Software Failure
28
PROFINET alarms
Default Fault Action
Same As Group 2
August 2015
Chapter 14. Diagnostics
16
Configurable
Diagnostic
No
Diagnostic
No
N/A
No
N/A
No
Diagnostic
Yes
N/A
No
17
No
N/A
No
Diagnostic
No