PROFINET Controller Faults in the PACSystems Fault
Tables
The PROFINET Controller logs all (Local, Controller, I/O) faults in its Local Log. In addition, it passes Controller
and I/O faults to the PACSystems CPU where they are logged in the corresponding CPU fault Tables (the
Controller Fault Table or the I/O Fault Table).
5.9.1

Clearing the PACSystems Fault Tables

Clearing one or both of the CPU's fault tables has no effect on the Local Log table in the PROFINET
Controller. The Local Log in the PROFINET Controller can only be cleared via a CLI command (applies to
PNC001-Ax module only).
Clearing one or both of the CPU's fault tables has no effect on the Diagnosis conditions maintained by any
IO-Device.
When the PACSystems CPU's fault tables are cleared, PROFINET-related faults are NOT re-reported, even
if the condition that is causing the fault still exists.
5.9.2

Faults Reported to the PACSystems Controller Fault Table

The following PROFINET Controller-related faults are reported in the Controller Fault Table of the PACSystems
CPU, in addition to being listed in the Local Log Table of the PROFINET Controller.
Group-
Error
Description
Code
Unable to deliver
11-67
configuration to
module.
11-81
Valid module
substitution
detected.
11-82
Module
configuration
mismatch during
configuration.
116
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
Cause
PROFINET Controller has
been configured for
feature(s) that are not
supported by the version
of PROFINET Controller
firmware in use
A module configured for a
PROFINET device does not
exactly match what is
physically present on the
device, but the device
indicates it is a valid
substitution.
A module configured for a
PROFINET device does not
match the module that is
physically present on the
device.
Recommended Correction
Upgrade the PROFINET Controller to its
latest firmware or disable unsupported
feature(s) configured for the PROFINET
Controller. The features supported for each
firmware revision can be found in the RX3i
PROFINET Scanner Important Product
Information, GFK-2573. This document may
be found on the support website.
The module should operate properly in the
presence of this fault. However, to eliminate
the fault, try one or more of the following:
Make sure the module is installed in the
correct location and move if necessary
(PNC001 only).
Update the configuration stored to the
PROFINET Controller to exactly match the
module present.
Replace the module on the device to match
the configuration.
The module will not operate properly,
therefore try one or more of the following:
Make sure the module is installed in the
correct location and move if necessary
(PNC001 only).
Update the configuration stored to the
PROFINET Controller to equal the actual
module present
Replace the module on the device to match
configuration.