PROFINET IO-Controller Diagnostics

10.8
This section describes:
Problems During Power-up
Status Reporting
Fault Contacts
PROFINET I/O Alarms
PROFINET IO-Controller Faults in the RXi Fault Tables
-
-
-

10.8.1 Power-up and Reset

During power-up and reset, the PNC runs diagnostics and initializes its hardware
components. When the necessary hardware components have been initialized and tested,
the PNC transitions to normal operation.

10.8.2 PROFINET IO-Controller Status Reporting

The PNC provides 32 bits of status information to a configured location in the RXi CPU's
reference memory.
The status data consists of the Module OK bit, which indicates the health of the PNC itself, a
status bit for each external port, and a bit that indicates the connection status of the
configured devices.
All Status bits are active high. The status location may be configured in %I, %Q, %AI, %AQ,
%R, %G, %T, %M or %W or I/O Variable reference memory in the RXi CPU.
Bit
1
2
3
4
5
6-8
9
10-32 Reserved
9
Individual device statuses (as reported by the PNIO_DEV_COMM function block) are updated prior to
the All Devices Connected bit. Therefore, it is possible (depending on PNC loading) to see via the
PNIO_DEV_COMM function block that every individual device is connected while the All Devices
Connected bit is not yet set. To avoid this inconsistency, it is recommended that the All Devices
Connected bit be checked first, before checking individual device connection status using the
PNIO_DEV_COMM function block.
For details on using the PNIO_DEV_COMM function block, refer to Section 10.7.2,
PNIO_DEV_COMM Function Block.
GFK-2816F
Clearing the RXi Fault Tables
Faults Reported to the RXi Controller Fault Table
Faults Reported to the RXi I/O Fault Table
Name
Module OK
Indicates the health of the PNC
1 indicates the PNC is functioning properly.
0 indicates the PNC is powering up or has failed.
Port1 Link
1 indicates the port is connected to another device and is operating correctly.
Up
0 indicates the port is not connected to another device or has an error
preventing communications.
Port2 Link
1 indicates the port is connected to another device and is operating correctly.
Up
0 indicates the port is not connected to another device or has an error
preventing communications.
Reserved
Reserved. Always 0.
Reserved
Reserved. Always 0.
Reserved
Reserved. Always 0.
All Devices
1 indicates all configured devices are connected and communicating over
9
Connected
PROFINET.
0 indicates no devices are configured or one or more configured devices
have not established a PROFINET connection.
Set to 0
Chapter 10. PROFINET IO-Controller Operation
Description
August 2015
215