Chapter 14. Diagnostics
Group/
Category
Type/
Error Code
9-6-10-0
Multiple Media Redundancy
Managers have been
detected on the network.
9-6-11-0
Multiple Media Redundancy
Managers are no longer
present on the network.
9-6-12-0
The Media Redundancy
Manager has detected that
the network ring has been
broken.
9-6-13-0
The Media Redundancy
Manager has detected that
the network ring has been
repaired.
9-11-3-1
Invalid MAC address
detected.
9-11-3-3
Media redundancy
configuration error.
18
9-11-5-x
Internal runtime error.
9-18-1-1
PNC exceeded its
recommended operating
temperature.
9-18-1-2
Watchdog Timeout Error
9-69-0-0
PNC has become heavily
loaded.
18
X – Type value will be equal to the Channel Error Type field of the PROFINET Alarm.
Y – Description value will be equal to the Extended Channel Error Type field of the PROFINET Alarm.
288
Description
The PNC is configured as a Media
Redundancy Manager and other
Media Redundancy Managers are
currently present on the network.
The PNC is configured as a Media
Redundancy Manager and it had
detected that multiple Media
Redundancy Managers were on
the network, but now those other
managers are no longer present.
The PROFINET MRP network ring
is broken.
The PROFINET MRP network ring
is closed/okay.
PNC no longer has a valid MAC
address.
The PNC has encountered a
problem attempting to configure
media redundancy operation.
PNC has encountered an internal
error during its operation.
The temperature detected by the
PNC has exceeded its safe
operating temperature.
PNC application code restarted
due to a hardware watchdog
timeout.
The PNC has become heavily
loaded with activity (Continued use
in this mode may cause
degradation of system
performance (possibly including
delayed IO updates) and potential
loss of network communications.
PACSystems* RXi Distributed IO Controller User Manual
Cause
Recommended Correction
Update the PNC configuration to
change its MRP role to either
Disabled or Client, or remove all
of the other devices on the
network that are also acting as a
Media Redundancy Manager.
No action necessary. The
network is expected to only
have a single Media
Redundancy Manager present.
The MRP Ethernet ring is
broken. Possible causes include
damaged or disconnected cable
or power loss to a node or
switch. Locate and repair the
cause(s).
No action necessary. This is the
normal, expected state of an
MRP Ethernet ring.
Contact customer service.
Contact customer service.
Contact customer service.
Reduce the temperature of the
environment where the PNC is
operating.
Contact customer service.
Reduce load on PNC. One or
more of the following can be
tried to reduce load:
Increase the configured
update rate value (i.e. IO
received less frequently) of
one or more PROFINET
Devices configured on the
PNC.
Reduce the number of
PROFINET Devices
configured on the PNC.
GFK-2816F