Encoder system connection
9.7 Sensor Module Cabinet-Mounted SMC40
9.7.2.4
X524 Electronics power supply
Table 9-24
Type: Spring-loaded terminal 6 (Page 320)
The maximum cable length is 30 m.
Note
The two "+" and/or "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
270
X524: Electronics power supply
Terminal Function
+
Electronics power supply (24 V)
+
Electronics power supply (24 V)
M
Electronics ground (0 V)
M
Electronics ground (0 V)
Technical data
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: max. 0.35 A
(with encoder system)
Maximum current via jumper in connec‐
tor: 20 A (15 A according to UL/CSA)
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2