Terminal Modules
6.6 Terminal Module TM54F
6.6.7
Protective conductor connection and shield support
It is always advisable to shield the digital input and output wiring.
The following diagram shows a typical Weidmüller shield connection clamp for the shield
support.
①
②
Figure 6-22
NOTICE
Damage or faulty operation due to incorrect shielding or inadmissible cable lengths
If the correct shielding procedures or the permissible cable lengths are not observed, it can
cause damage or the machine may malfunction.
• Only use shielded cables.
• Do not exceed the cable lengths stated in the technical data.
6.6.8
Technical data
Table 6-46
6SL3055-0AA00-3BA.
Electronics power supply
Voltage
Current X524 (without DRIVE-CLiQ)
Current X514 (without DRIVE-CLiQ and digital outputs)
Power loss
Sensor power supply with and without forced dormant error detection (L1+, L2+, L3+)
Voltage
176
Shield connection terminal, Weidmüller company, type: KLBUE CO1, Article number:
1753311001
Protective conductor connection M4 / 1.8 Nm (15.9 lbf in)
Protective conductor connection and shield support
Technical data
Unit
Value
V
24 (20.4 ... 28.8)
DC
A
≤0.2
DC
A
≤0.05
DC
W
≤5
V
24 (20.4 ... 28.8)
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2