X150 P1/P2 Profinet; Measuring Socket - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Control Units and operating elements
4.3 Control Unit CU320-2 PN (PROFINET)
4.3.2.8

X150 P1/P2 PROFINET

The PROFINET interfaces can be operated isochronously.
Table 4-9
8
1
Connector type: RJ45 socket
Cable type: PROFINET
Note
The PROFINET interfaces support Auto MDI(X). It is therefore possible to use both crossed and
uncrossed cables to connect the devices.
For diagnostic purposes, the two PROFINET interfaces are equipped with a green and a yellow
LED. These LEDs indicate the following status information:
Table 4-10
LED
Link port
Activity port
4.3.2.9

Measuring socket

Table 4-11
Measuring socket with mounted PC board connector
Socket
M
M
T0
T1
T2
T0
T1
T2
PCB plug connector from Phoenix Contact, type: ZEC 1.0/ 4-ST-3.5 C1 R1.4, Article number: 1893708
58
X150 P1 and X150 P2 PROFINET
Pin
Signal name
1
RXP
2
RXN
3
TXP
4
Reserved, do not use
5
Reserved, do not use
6
TXN
7
Reserved, do not use
8
Reserved, do not use
LED states at the X150 P1/P2 PROFINET interface
Color
Status
-
Off
Green
Continuous light
-
Off
Yellow
Flashing light
Function
Ground
Measuring terminal 0
Measuring terminal 1
Measuring terminal 2
Technical data
Receive data +
Receive data -
Transmit data +
-
-
Transmit data -
-
-
Description
Missing or faulty link
10 or 100 Mbit link available
No activity
Data is being received or sent at port x
Technical data
Voltage: 0... 5 V
Resolution: 8 bits
Load current: max. 3 mA
Continuous short-circuit proof
The reference potential is terminal M
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2