Connection example 2: HTL encoder, unipolar, with reference signal
Figure 9-15
Because the physical transmission media is more robust, the bipolar connection should always
1)
be used. The unipolar connection should only be used if the encoder type does not output
push-pull signals.
Figure 9-16
The photo above shows the wire jumpers for connecting unipolar HTL encoders with a reference
signal.
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
K1
K2
K3
Ub
M
Connection example 2: HTL encoder, unipolar, with reference signal
Photo of connection example 2: SMC30, 30 mm wide
Encoder system connection
9.6 Sensor Module Cabinet-Mounted SMC30
X521
1
Track A
2
Track A*
3
Track B*
4
Track B*
5
Reference signal R
6
Reference signal R*
7
CTRL
8
Ground
X531
1
GeberversEncoder power supply 24 V
2
Ground for encoder power supply
1)
257