Protective Conductor Connection And Shield Support; Technical Specifications - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

9.6.7

Protective conductor connection and shield support

Shield contacts are only required if the system is connected to X521/X531.
1
Figure 9-19
The bending radii of the cables must be observed (see MOTION-CONNECT description).
NOTICE
Damage or faulty operation due to incorrect shielding or inadmissible cable lengths
If the correct shielding procedures or the permissible cable lengths are not observed, it can
cause damage or the machine may malfunction.
• Only use shielded cables.
• Do not exceed the cable lengths stated in the technical data.
9.6.8

Technical specifications

Table 9-18
Technical specifications
6SL3055-0AA00-5CA2
Electronics power supply
Voltage
Current (without encoder system)
Power loss
Max. cable length
Encoder system power supply
Voltage
Current
Encoder frequency that can be evaluated
(f
)
encoder
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
2
Shield connection terminal, Weidmüller company, type: KLBUE CO1, Article number:
1753311001
Protective conductor connection M4 / 1.8 Nm (15.9 lbf in)
Protective conductor connection and shield support
Unit
V
DC
A
DC
W
m
V
DC
A
DC
kHz
9.6 Sensor Module Cabinet-Mounted SMC30
Value
24 (20.4 ... 28.8)
≤ 0.2
≤ 4
30
5 (with or without remote sense)
0.35
≤ 500
Encoder system connection
or V
- 1 V
1)
DC
261

Advertisement

Table of Contents
loading

This manual is also suitable for:

6sl3055-0aa00-5ea

Table of Contents