8.11

Service and maintenance

Replacing the Voltage Sensing Module VSM10 in Smart Line Modules Chassis and Active Interface
Modules Chassis
When replacing a Voltage Sensing Module VSM10 in an Active Interface Module Chassis or
Smart Line Module Chassis, observe the following application cases:
1. Replacing a VSM10 with article number 6SL3053-0AA00-3AA0 by a VSM10 with article
number 6SL3053-0AA00-3AA1:
It is NOT permissible that the connector jumper
VSM10 is removed!
2. Replacing a VSM10 with article number 6SL3053-0AA00-3AA1 by a VSM10 with article
number 6SL3053-0AA00-3AA1:
Proceed with the connector jumper
the same as at the previously installed VSM10.
Electric shock due to incorrect replacement of spare parts
If you remove the connector jumper at terminal X530 when replacing a VSM10 with article
number 6SL3053-0AA00-3AA0 by a VSM10 with article number 6SL3053-0AA00-3AA1, then
a hazardous voltage is present in the Active Interface Module Chassis or Smart Line Module
Chassis. Touching live components can result in death or severe injury.
• When replacing the VSM10 proceed as specified above.