9.5.3

Connection example

Figure 9-9
9.5.4

Meaning of the LED

Table 9-11
Meaning of the LEDs on the Sensor Module Cabinet-Mounted SMC20
LED
Color
RDY
-
READY
Green
Orange
Red
Green / Red
Green /
Orange
or
Red /
Orange
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
Connection of an encoder system via a Sensor Module Cabinet-Mounted (SMC) for a motor
without a DRIVE-CLiQ interface
Status
Off
The electronics power supply is missing or outside the permis‐
sible tolerance range.
Continuous
The component is ready for operation. Cyclic DRIVE-CLiQ com‐
light
munication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
This component has at least one fault.
light
Note:
The LED is activated irrespective of whether the corresponding
messages have been reconfigured.
Flashing
Firmware is being downloaded.
light
0.5 Hz
Flashing
Firmware download is complete. The system waits for POWER
light
ON.
2 Hz
Flashing
Component recognition via LED is activated (p0144=1).
light
Note:
2 Hz
Whether the LED flashes green/orange or red/orange depends
on the status the LED had during activation (setting of param‐
eter p0144 to "1").
9.5 Sensor Module Cabinet-Mounted SMC20
Description, cause
Encoder system connection
Remedy
Remove and ac‐
knowledge the fault.
Carry out a POWER
ON.