Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
P1-09
High Feedback Level
0608
High FB Level
High Feedback Level Fault
P1-10
0609
Delay Time
Hgh Lvl Flt Time
P1-11
Maximum SetPoint
0106
Difference
Max Set-point Diff
<0032>
P1-12
Not Maintaining Set-point
0107
Time
Not Maint SP Tm
<0032>
P1-13
Hysteresis Level
0108
Hysteresis Level
P1-14
Prime Loss Level
0109
Prime Loss Level
Low/Hi Water Digital
Input Configuration
P1-15
010A
Water DI Config
<0034>
P1-16
Loss of Prime Time
87F
Prime Loss Time
<0034>
Denotes that parameter can be changed when the drive is running.
Sleep Level Type
P2-01
060A
Sleep Lvl Type
72
Display
The drive will display a "High Feedback Level (HFB)" alarm when the
feedback level rises above the programmed level. The alarm will turn off
when the feedback level falls below the programmed High Feedback Level
minus the Hysteresis Level (P1-13). This function is active during running
in the hand mode, auto mode, pre-charge and thrust-bearing mode.
If P1-01 = 3, parameter P9-18 uses this value to calculate the quick de-
stage feedback level.
The drive will initiate a "High Feedback Fault (HFB)" when the feedback
level rises above the programmed level for a time specified in P1-10. The
drive will coast to a stop when a fault occurs. This function is active during
running in all operation modes.
If P1-01 = 3, the function will stop all drives running on the network when
the system fault occurs.
When the drive is running and the difference between the setpoint and the
feedback exceeds the level in P1-11 for the time specified in P1-12, the
drive will trip on a "Not Maintaining Set-point (NMS)". The drive will
coast to a stop when a fault occurs. A value of 0 disables this function. This
function is only active during running while operating in auto mode.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives
running on the network when the system fault occurs.
Delay time before a Not Maintaining Set-point fault occurs. Pump
protection criteria specified in P1-11 must be met for the drive to fault. The
drive will coast to a stop when a fault occurs. A value of 0 disables Not
Maintaining Set-point fault.
Hysteresis Level used for low and high feedback alarm detection. See
function P1-07 and P1-09.
Used to detect loss of prime in the pump. If output current drops below this
level for the time specified in P1-12 and the output frequency is at fmax, a
"Loss Of Prime" fault occurs. The drive will coast to a stop when a fault
occurs.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives
running on the network when the system fault occurs.
Sets the type of control operation
0: Low N.O. - Hi N.O. (Low Water Normally Open, High Water Normally
Open)
<0034>
1: Low N.C. - Hi N.O. (Low Water Normally Closed, High Water
Normally Open)
2: Low N.O. - Hi N.C. (Low Water Normally Open, High Water Normally
Closed)
<0034>
3: Low N.C. - Hi N.C.(Low Water Normally Closed, High Water Normally
Closed)
<0034>
To use the low water function one of the digital inputs (H1-
be programmed. The low water input can be used for a low water condition
or in combination with the pre-charge function to indicate the reservoir is
filled. The low water input fault is only active during running while
operating in auto mode.
Delay time before a Loss of Prime fault occurs. Pump protection criteria
specified P1-14 must be met for the drive to fault. On fault the drive will
coast to a stop.
Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
3: Output Speed (rpm)
4: Low Flow (Terminal A1 - Flow meter required)
Note: Feedback depends on PID direction operation.
Displays a "Sleep" Alarm when active.
Description
<0034>
<0034>
<0034>
Pump Protection
<0034>
<0034>
Setting
Range
0.0 ~
6000.0
(system
units
P1-02)
0 ~ 3600
sec
0.0 ~
6000.0
(system
units
P1-02)
<0034>
0 ~ 3600
sec
0.0 ~ 100.0
(system
units
P1-02)
0.0 ~
1000.0 A
<0034>
0 ~ 3
=85) must
1 ~ 600 sec
0 ~ 4
YASKAWA TM.iQp.10 Technical Manual Supplement
Factory
Menu
Setting
Location
155.0
(system
Programming
units
P1-02)
2 sec
Programming
0.0 (system
units
Programming
P1-02)
60 sec
Programming
0.0 (system
units
Programming
P1-02)
0.0 A
Programming
0
Programming
20 sec
Programming
0
Programming