YASKAWA iQpump Manual Supplement page 67

Intelligent pump controller
Table of Contents

Advertisement

Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Speed Agreement
L4-01
0499
Detection Level
Spd Agree Level
Speed Agreement
L4-02
049A
Detection Width
Spd Agree Width
Frequency Reference Loss
L4-05
049D
Detection Selection
Ref Loss Sel
Frequency Reference
L4-06
04C2
Level at Loss Frequency
Fref at Freq loss
Number of Auto Restart
L5-01
049E
Attempts
Num of Restarts
Auto Restart Operation
L5-02
049F
Selection
Restart Sel
Maximum Restart Time
L5-03
04A0
After Fault
Max Restart Time
YASKAWA TM.iQp.10 Technical Manual Supplement
Display
L4-01 and L4-02 are used in conjunction with the multi-function outputs,
(H2-01and H2-02) as a setpoint and hysteresis for a contact closure.
Determines how the drive will react when the frequency reference is lost.
0: Stop (Disabled) - Drive will not run at the frequency reference.
1: Enabled @ % of PrevRef - Drive will run at a percentage (L4-06) of the
frequency reference level at the time frequency reference was lost.
Note: Only available in the Hand Mode (P5-01 = 0).
If Frequency Reference loss function is enabled (L4-05 = 1) and Frequency
Reference is lost, then the drive will run at reduced frequency reference
determined by L4-06. New Fref=Fref at time of loss x L4-06.
Note: Only available in the Hand Mode (P5-01 = 0)
Determines the number of times the drive will perform an automatic
restart.
Determines if the fault contact activates during an automatic restart
attempt.
0: No Flt Relay - fault contact will not activate during an automatic restart.
1: Flt Relay Active - fault contact will activate during an automatic restart.
If the restart fails (or is not attempted due to a continuing fault condition,
e.g. an OV fault) the drive waits the Maximum Restart Time After Fault
(L5-03) before attempting another restart. This parameter is not applicable
to Loss of Prime Fault.
Description
Reference Detection
Fault Restart
Setting
Factory
Menu
Range
Setting
Location
0.0 ~
0.0 Hz
Programming
200.0 Hz
0.0 ~
2.0 Hz
Programming
20.0 Hz
0 ~ 1
0
Programming
0 ~ 1
0
Programming
0 ~ 10
5
Programming
0 ~ 1
0
Programming
10.0 ~
3600.0 sec
20.0 sec
Programming
<0032>
67

Advertisement

Table of Contents
loading

Table of Contents