Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Torque Detection
L6-01
04A1
Selection 1
Load Detection
Torque Detection Level 1
L6-02
04A2
Load Det Lvl
Torque Detection Time 1
L6-03
04A3
Loss Det Time
Internal Dynamic Braking
Resistor Protection
L8-01
04AD
Selection
DB Resistor Prot
Overheat Pre-Alarm Level
L8-02
04AE
OH Pre-Alarm Lvl
Overheat Pre-Alarm
L8-03
04AF
Operation Selection
OH Pre-Alarm Sel
Input Phase Loss
L8-05
04B1
Protection Selection
<0033>
Ph Loss In Sel
Input Phase Loss
L8-06
04B2
Detection Level
Ph Loss In Lvl
Output Phase Loss
L8-07
04B3
Protection Selection
<0033>
Ph Loss Out Sel
Output Ground Fault
L8-09
04B5
Detection Selection
Ground Fault Sel
Heatsink Cooling Fan
L8-10
04B6
Operation Selection
Fan On/Off Sel
Heatsink Cooling Fan
L8-11
04B7
Operation Delay Time
<0032>
Fan Delay Time
Ambient Temperature
L8-12
04B8
Setting
Ambient Temp
68
Display
Determines the drive's response to an overtorque/undertorque condition.
Overtorque and Undertorque are determined by the settings in parameters
L6-02 and L6-03.
0: Disabled
1: OL@SpdAgree - Alm (Overtorque Detection only active during Speed
Agree and Operation continues after detection)
2: OL At RUN - Alm (Overtorque Detection is always active and operation
continues after detection)
3: OL@SpdAgree - Flt (Overtorque Detection only active during Speed
Agree and drive output will shut down on an OL3 fault.)
4: OL At RUN - Flt (Overtorque Detection is always active and drive
output will shut down on an OL3 fault.)
5: LL@SpdAgree - Alm (Undertorque Detection is only active during
Speed Agree and operation continues after detection.)
6: LL at RUN - Alm (Undertorque Detection is always active and
operation continues after detection.)
7: LL @ SpdAgree - Flt (Undertorque Detection only active during Speed
Agree and drive output will shut down on an OL3 fault.)
8: LL At RUN - Flt (Undertorque Detection is always active and drive
output will shut down on an OL3 fault.)
Sets the overtorque/undertorque detection level as a percentage of drive
rated current.
Sets the length of time an overtorque/undertorque condition must exist
before being recognized by the drive. OL3 is then displayed.
0: Not Provided
1: Provided
When the cooling fin temperature exceeds the value set in this parameter,
an overheat pre-alarm (OH) will occur.
Drive Operation upon OH Pre Alarm Detection.
0: Ramp to Stop (Decel Time C1-02).
1: Coast to Stop
2: Fast-Stop (Decel Time = C1-09).
3: Alarm Only
*0 to 2 is recognized as fault detection, and 3 is recognized as alarm. (For
the fault detection, the fault contact operates.)
4: OH Alarm & Reduce (Continue operation and reduce output frequency
by L8-19)
Selects the detection of input current phase loss, power supply voltage
imbalance, or main circuit electrostatic capacitor deterioration.
0: Disabled
1: Enabled
Monitors the DC Bus current ripple and activates when one of the input
phases is lost (PF).
Selects the detection of output current open-phase.
When applied motor capacity is too small for drive capacity, output phase
loss may be detected inadvertently. In this case, set to 0.
0: Disabled
1: Enabled
Enables and disables drive output ground fault detection.
0: Disabled
1: Enabled
Controls the Heatsink Cooling Fan Operation.
0: Fan On-Run Mode (Fan will operate only when drive is running and for
L8-11 seconds after RUN is removed).
1: Fan Always On (Cooling fan operates whenever drive is powered up.)
When L8-10=0 this parameter sets a delay time for Cooling Fan de-
energization after the run command is removed or baseblock enabled.
When the drive is installed in an ambient temperature exceeding its rating,
drive overload (OL2) protection level is reduced.
Description
Torque Detection
Hardware Protection
Setting
Factory
Range
Setting
0 ~ 8
0
0 ~ 300 %
15 %
0.0 ~
10.0 sec
10.0 sec
0 ~ 1
0
50 ~
95 °C
130 °C
0 ~ 4
4
0 ~ 1
1
kVA
0.0 ~ 25.0
Dependent
0 ~ 1
1
0 ~ 1
1
0 ~ 1
0
0 ~ 300 sec
300 sec
45 ~ 60 °C
45 °C
YASKAWA TM.iQp.10 Technical Manual Supplement
Menu
Location
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming