YASKAWA iQpump Manual Supplement page 88

Intelligent pump controller
Table of Contents

Advertisement

Addr.
Parameter No.
Hex
U1-16
004F
U1-18
0051
U1-20
0053
U1-24
0057
U1-28
005B
U1-29
005C
U1-30
005D
U1-34
0061
U1-36
0063
U1-37
0064
U1-38
0065
U1-39
0066
U1-40
0067
U1-62
007D
U1-67
009B
U1-68
0009C
U1-80
009Dh
<0035>
U1-90
0720
88
Parameter Name Digital
Operator Display
Terminal A2 Input Voltage
Term A2 level
Motor Secondary Current (Iq)
Mot SEC Current
Output Frequency After Soft
Start
SFS Output
PI Feedback Value
PI Feedback
CPU Number
CPU ID
kWh
kWh Lo 4 Digits
MWh
kWh Hi 5 Digits
First Parameter Causing an OPE
OPE Detected
PI Input
PI Input
PI Output
PI Output
PI Set-point
PI Set-point
Memobus Communication Error
Code
Transmit Err
Heatsink Cooling Fan Operation
Time
FAN Elapsed Time
Running Queue No
Running Queue No
Network Activity
Network Activity
Time to Alternate
Time to Alternate
Geothermal Temperature Input
Geothermal Temp
Pump Set-point
Pump Set-point
Displays the input current (or voltage) on Terminal A2, as a percentage of 20 mA (or 10 Vdc).
Displays the amount of current being used by the motor to produce torque (Iq).
Displays the frequency reference (speed command) after the accel and decel ramps.
Displays the feedback signal when PI control is used.
Displays control board hardware revision.
Displays the accumulated kWh.
Displays the accumulated MWh.
Displays the parameter number causing an "OPE" fault.
Displays the "error" in the PI regulator. (U1-36 = PI Set-point - PI Feedback).
Displays the output of the PI as a percentage of maximum frequency (E1-04).
Displays the setpoint of the PI regulator (U1-38 = PI reference + PI bias).
0 0 0 0 0 0 0 0
Displays total operating time of the heatsink cooling fan.
Position in the iQpump Memobus Multiplex Running Queue
Shows network traffic. A fluctuating number from 0 to 1000 denotes activity, while a
relatively constant 0 denotes no activity.
Unit changes based on network status:
<->: Drive can not communicate to other drives
<+>: Drive is a Node on a network
<M>: Drive is a Master on an iQpump Network
Time remaining before a drive requests alternation which is dependent on P9-04.
Geothermal temperature input after the gain and bias has been applied. This is the temperature
used by the Geothermal Function to determine what frequency to run the drive.
Internally limited to -999.9°F and 999.9°F.
Only shown when B1-05 = 5
Units 0.1°F
Displays drive setpoint.
Resolution 0.1
Note: Does not include setpoint compensation (U1-93).
Description
Monitor
1: CRC error
1: Data length error
Not used. Always 0.
1: Parity error
1: Overrun error
1: Framing error
1: Timeover
Not used. Always
0.
YASKAWA TM.iQp.10 Technical Manual Supplement

Advertisement

Table of Contents
loading

Table of Contents