YASKAWA iQpump Manual Supplement page 79

Intelligent pump controller
Table of Contents

Advertisement

Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Low City Pressure Input
P4-21
834
Select
<0034>
Low City In Sel
P4-22
Low City Pressure Input
835
Delay
Low City Delay
<0034>
P4-23
Lube Pump Delay Timer
836
Lube Pump Time
<0034>
P4-24
Remote Drive Disable
837
Selection
Rem Drv Dis Sel
<0035>
P4-25
Remote Drive Disable
838
On-Delay
Drv Dis On-Delay
<0035>
P4-26
Remote Drive Disable
839
Off-Delay
Drv Dis Off-Delay
<0035>
P4-27
Low City Alarm Text
83
Low Cty Alrm Txt
<0035>
P4-31
Minimum Geothermal
83B
Temperature Inpu
MinGeothrm Scale
<0035>
P4-32
Maximum Geothermal
83C
Temperature Inpu
MaxGeothrm Scale
<0035>
P4-33
Minimum Geothermal
83D
Speed
MinGeothrm Speed
<0035>
P4-34
Maximum Geothermal
83E
Speed
MaxGeothrm Speed
<0035>
Low Temperature to
P4-35
Run at Maximum
83F
Geothermal Speed
<0035>
Low Temp @ Max
Low Temperature to
P4-36
Run at Minimum
85B
Geothermal Speed
<0035>
Low Temp @ Min
Low Temperature to
P4-37
Run at Minimum
85C
Geothermal Speed
<0035>
Low Temp @ Min
High Temperature to
P4-38
Run at Maximum
85D
Geothermal Speed
<0035>
High Temp @ Max
P4-39
Geothermal Temperature
85E
Loss Detection
Geotherm Loss Det
<0035>
YASKAWA TM.iQp.10 Technical Manual Supplement
Display
Selects the type of pressure switch connected to the "Low City Pressure"
digital input (H1-0x = 73).
0: Normally Open (closed indicates the "Low City Pressure"
condition)
1: Normally Closed (open indicates the "Low City Pressure"
condition)
Sets the amount of time a "Low City Pressure" condition must be present
before the drives will stop. Also sets the amount of time that the pressure
must be adequate before the drive system will re-start.
Sets the amount of time the drive's output will be delayed and the Lube
Pump digital output (H2-0x = 55) will be energized.
A setting of zero will disable this feature.
Selects the type of pressure switch connected to the "Remote Drv Disbl"
digital input (H1-0 =72).
0: Normally Open (closed indicates the "Remote Drive Disable"
condition).
1: Normally Closed (open indicates the "Remote Drive Disable"
condition).
Sets the amount of time a "Remote Drive Disable" condition must be
present before the drive will stop.
Sets the amount of time a "Remote Drive Disable" condition must be
absent before the drive will be allowed to run.
Selects the alarm message that will be displayed when a Low City
condition is detected.
0: Low City Pressure
1: Low Suction Pressure
2: Low Water in Tank
Parameter functionality stated below only applies when b1-01 = 5 (Geothermal Mode)
Sets the temperature that corresponds to a 0V (or 4 mA) analog input.
Sets the temperature that corresponds to a 10V (or 20 mA) analog input.
Frequency Reference (Hz)
Sets the frequency reference characteristics based on the set temperature
points and the corresponding frequency.
For proper operation, P4-34>P4-33 and P4-38>P4-37>P4-36>P4-35.
See Function Description for more information.
Selects the drive action when the signal from Terminal A2 has gone below
3 mA or above 21 mA. Only effective when H3-08 = 2
(4-20 mA) and H3-09 = 20 (Geothermal Temp).
0: Disabled
1: Alarm
2: Fault
Description
P4-34
P4-33
P4-36 P4-38
P4-35
P4-36
°
Temperature (
F)
Setting
Factory
Menu
Range
Setting
Location
0 ~ 1
1
Programming
1 ~ 1000
10 sec
Programming
sec
0.0 ~
0.0 sec
Programming
300.0 sec
0.0 ~ 1
0.0 sec
Programming
0 ~ 1000
0 sec
Programming
sec
0 ~ 1000
0 sec
Programming
sec
0 ~ 2
0 sec
Programming
-110.0 ~
0.0
Programming
440.0 °F
-110.0 ~
150.0
Programming
450.0 °F
0.00 ~
40.00 Hz Programming
120.00Hz
0.00 ~
60.00 Hz Programming
120.00Hz
-110.0 ~
55.0
Programming
450.0 °F
-110.0 ~
65.0
Programming
450.0 °F
-110.0 ~
75.0
Programming
450.0 °F
-110.0 ~
85.0
Programming
450.0 °F
0 ~ 2
1
Programming
79