13 Transducer Wiring using an External Power Supply
Triplex System: Transducer Connection using Analog Input A1
A2 used for pressure transducer.
24Vdc Power Supply
V+
Output
4-20mA
Transducer
*
Resistor 250 Ohm / 1% 1W
Refer to Page 242 of the
TM.iQp.06 User Manual for
gain and bias settings.
50
External Power Supply only
External
required when connecting 2
or more drives.
+ -
iQpump 1
+V
A1
*
250
AC
EG
iQpump 2
A1
AC
EG
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
iQpump x
A1
AC
EG
Last drive on network