YASKAWA iQpump Manual Supplement page 59

Intelligent pump controller
Table of Contents

Advertisement

Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
H1-04
Terminal S6 Function
(continued
0403
Selection
on next
Terminal S6 Sel
page)
YASKAWA TM.iQp.10 Technical Manual Supplement
Display
26: External Pump Fault, Normally Open, During Run, Coast To Stop
27: External Pump Fault, Normally Closed, During Run, Coast To Stop
28: External Pump Fault, Normally Open, Always Detected, Fast-Stop
29: External Pump Fault, Normally Open, Always Detected, Fast-Stop
2A: External Pump Fault, Normally Open, During Run, Fast-Stop
2B: External Pump Fault, Normally Closed, During Run, Fast-Stop
2C: External Pump Fault, Normally Open, Always Detected, Alarm Only
2D: External Pump Fault, Normally Closed, Always Detected, Alarm Only
2E: External Pump Fault, Normally Open, During Run, Alarm Only
2F: External Pump Fault, Normally Closed, During Run, Alarm Only
30: PID Integral Reset
31: PID Integral Hold
34: PI SFS Cancel
36: Option/Inv Sel 2
Selects source of speed command and sequence.
Closed = Option Card, Open = b1-01 & b1-02.
60: Motor Preheat Applies current to create heat to avoid condensation.
Closed = Apply amount of current as set in parameter b2-09.
61: Speed Search 1
When closed as a run command is given, drive does a speed
search starting at maximum frequency (E1-04). (Current detection.)
62: Speed Search 2
When closed as a run command is given, drive does a speed
search starting at speed command. (Current detection.)
64: Speed Search 3
67: Com Test Mode - Used to test RS-485/422 interface.
Direction determined by fwd/rev input. 3-wire control Only.
6A: Drive Enable - Closed = Drive will accept run command.
Open = Drive will not run. If running, drive will stop per b1-03.
6B: Com/Inv Sel - Selects source of speed command and sequence
Closed = Serial Communication (R+,R-,S+,S-), Open = b1-01 & b1-02
6C: Com/Inv Sel 2
72: Remote Drv Disbl <0035>
Prevents the drive from running when active for the time set in P4-25.
Must be inactive for the time set in P4-26 to allow the drive to run again.
Note: Parameter P4-24 determines if this input is Normally Open or
Normally Closed.
73: Low City Press
Indicates that sufficient/insufficient pressure is present on the inlet to the
pump. Used mainly for pressure booster stations. When P1-01 = 3, an
alarm condition (see parameters P4-21 and P4-22) will cause drives in the
network to stop running and show a "Net Pump Err" message. 75: Reset
Accum
<0034>
Closed: Volume accumulated will be reset to zero (and held at zero if
digital input remains closed).
76: High Water Level
Function will be active whenever the drive is running. Function logic
depends on parameter P1-15 (Water DI Config).
P1-15 = 0 or 1 (Normally Open)
Closed: High Water Level Fault
Open: Reservoir/Tank is filled to normal level.
P1-15 = 2 or 3 (Normally Closed)
Closed: Reservoir/Tank is filled to normal level.
Open: High Water Level Fault
80: Hand Mode
Function Active in Stopped and Auto Mode.
Closed: Hand mode operation as defined in P1-14.
Open: Stop Mode when with no incoming run command.
Note: Input not active when b1-02 is set for 0 – Operator.
81: Disable Sleep Mode
Function Active in Auto Mode.
Closed: Disables sleep function, Feedback Drop Detection and Over cycle
protection.
Open: Sleep function, Feedback Drop Detection and Over cycle protection
enabled.
82: Sleep Activation
Active in Auto Mode.
Closed: Drive will go to sleep (External Digital Input).
Open: No function.
Description
<0034>
<0034>
Setting
Factory
Menu
Range
Setting
Location
0 ~ 87
80
Programming
59