YASKAWA iQpump Manual Supplement page 75

Intelligent pump controller
Table of Contents

Advertisement

Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Drive Multi/Maximum
P3-02
0615
Level
Max-Multi Level
P3-03
Add Pump Delta Level
0616
Add Pump D-Lvl
P3-04
Add Pump Delay Time
0617
Add Pump Dly Tm
Shutdown Pump Delta
P3-05
0618
Level
Shdn Pump D-Lvl
Shutdown Pump Delay
P3-06
0619
Time
Shdn Pump Dly Tm
Multi Pump Set-point
P3-07
061A
Increase
MP Set-point Incr
Multi Pump Set-point
P3-08
061B
Decrease
MP Set-point Decr
Denotes that parameter can be changed when the drive is running.
YASKAWA TM.iQp.10 Technical Manual Supplement
Display
Sets the maximum level used for multiplex pumping operation. Parameter
is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-01 = 0: When the output frequency rises above the level programmed
in P3-02 for a time specified in P3-04, the next available pump will be
added to the system by means of a multi-function digital output closure
(H2-
= 40, 41).
P3-01 = 1: Not Used.
P3-01 = 2: When the output frequency rises above level programmed in
P3-02 and the delta feedback (setpoint minus feedback) has exceeded the
level programmed in P3-03 for a time specified in P3-04, the next available
pump will be added to the system by means of a multi-function digital
output closure (H2-
Sets the level used for multiplex pumping operation. The parameter is
active when P3-01 =1 or P3-01 = 2 is selected.
P3-01 = 0: Not Used
P3-01 = 1: When the delta feedback (setpoint minus feedback) has
exceeded the level programmed in P3-03 for a time specified in P3-04, the
next available pump will be added to the system by means of a multi-
function digital output closure. (H2-
P3-01 = 2: When the output frequency rises above level programmed in
P3-02 and the delta feedback (Set-point minus feedback) has exceeded the
level programmed in P3-03 for a time specified in P3-04, the next available
pump will be added to the system by means of a multi-function digital
output closure. (H2-
Note: Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
Sets the delay time before a pump is added to the system. Works in
conjunction with parameters P3-02, P3-03, and P2-11 to P2-19.
Sets the level used for multiplex pumping operation. Parameter is active
when P3-01 = 1 or P3-01 = 2 is selected.
P3-01 = 0: Not Used
P3-01 =1 : When the delta feedback (feedback minus setpoint) has
exceeded the level programmed in P3-05 for a time specified in
P3-06,the last pump that was brought online will be shutdown by means of
a multi-function digital output opening. (H2-
P3-01 = 2: When the output frequency drops below level programmed in
P3-09 or P3-10 (depends on last pump running) and the delta feedback
(feedback minus setpoint) has exceeded the level programmed in P3-05 for
a time specified in P3-06, the last pump that was brought online will be
shutdown by means of a multi-function digital output opening. (H2-
40, 41).
Note: Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
Sets the delay time before one of the additional across the line pumps is
shutdown.Works in conjunction with parameters P3-02 and P3-03.
Sets the amount the drive's setpoint will decrease for each time a new
pump is brought offline.
Pump 1: Set-point
Pump 1+2: Set-point + P3-07
Pump 1+2+3: Set-point + (2 x P3-07)
Sets the amount the drive's setpoint will increase for each time a new pump
is brought online.
Pump 1: Set-point
Pump 1+2: Set-point - P3-08
Pump 1+2+3: Set-point - (2 x P3-08)
Description
= 40, 41).
= 40, 41).
= 40, 41).
= 40, 41).
Setting
Factory
Menu
Range
Setting
Location
0.0 ~
59.0 Hz
Programming
120.00 Hz
0.0 ~
6000.0
0.0 (system
(system
units
Programming
units
P1-02)
P1-02)
0 ~ 3600
2 sec
Programming
sec
0.0 ~
6000.0
0.0 (system
(system
units
Programming
units
P1-02)
P1-02)
=
0 ~ 3600
5 sec
Programming
sec
0.0 ~
6000.0
0.0 (system
(system
units
Programming
units
P1-02)
P1-02)
0.0 ~
6000.0
0.0 (system
(system
units
Programming
units
P1-02)
P1-02)
75