Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Second Line User Monitor
o1-07
0518
Selection
2nd Monitor Sel
Third Line User Monitor
o1-08
0519
Selection
3rd Monitor Sel
Local/Remote Key
o2-01
0505
Function Selection
Local/Remote Key
OFF Key Function During
o2-02
0506
Auto Run
Oper OFF Key
User Parameter Default
o2-03
0507
Value
User Defaults
Drive/kVA Selection
o2-04
0508
Inverter Model #
Frequency Reference
Setting
o2-05
0509
Method Selection
Operator M.O.P.
Operation Selection when
Digital Operator is
o2-06
050A
Disconnected
Oper Detection
Cumulative Operation
o2-07
050B
Time Setting
Elapsed Time Set
Cumulative Operation
o2-08
050C
Time Selection
Elapsed Time Run
Cumulative Cooling Fan
o2-10
050E
Operation Time Setting
Fan ON Time Set
Fault Trace/Fault History
o2-12
0510
Clear Function
FLT Trace Init
kWh User Monitor (U1-
o2-14
0512
29) Initialization
kWh MonitorClear
Copy Function Selection
o3-01
0515
Copy Function Sel
Read Allowed Selection
o3-02
0516
Read Allowable
70
Display
Sets the "U1" monitor always displayed on the 4th line of the digital
operator display. Effective only when o1-06 = 1.
Sets the "U1" monitor always displayed on the 5th line of the digital
operator display. Effective only when o1-06 = 1.
Has no function when HOA operator is connected.
0: Disabled
1: Enabled
Determines if the off key on the digital operator will stop the drive when
drive is operating from external terminals or serial communications.
0: Disabled
1: Enabled
Allows storing of current parameter values as a User Initialization
Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as user initialization. A1-
03 now allows selecting <1110> for user initialization.
2: Clear All (Clears the currently saved user initialization. A1-03 no longer
allows selecting <1110>.
Sets the kVA of the drive. Enter the number based on drive model #. Use
the
portion of the CIMR-P7
Determines if the Data/Enter key must be used to input a frequency
reference from the digital operator.
0: Disabled - Data/Enter key must be pressed to enter a frequency
reference.
1: Enabled: -Data/Enter key is not required. The frequency reference is
adjusted by the up and down arrow keys on the digital operator without
having to press the data/enter key.
Determines if the drive will stop when the digital operator is removed.
0: Disabled - The drive will not stop when the digital operator is removed.
1: Enabled - The drive will fault (OPR) and coast to stop when the operator
is removed.
Sets the initial value of the elapsed operation timer.
Sets how time is accumulated for the elapsed timer (o2-07).
0: Power-On Time (Time accumulates whenever drive is powered).
1: Running Time (Time accumulates only when drive is running)
Sets the initial value of the heatsink fan operation time.
Clears the fault memory contained in the U2 and U3 monitors.
0: Disabled (no effect).
1: Enabled - resets U2 and U3 monitors, and returns o2-12 to zero.
Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change)
1: Clear all - Resets U1-29 to zero and returns o2-14 to zero.
This parameter controls the copying of parameters to and from the digital
operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from the drive to the
digital operator.
2: OP -> INV WRITE - All parameters are copied from the digital operator
into the drive.
3: OP <--> INV VERIFY - Parameter settings in the drive are compared to
those in the digital operator.
Note: When using the copy function, the drive model number and software
number (U1-14) must match or an error will occur.
Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are allowed.
1: Enabled - Copying allowed
Description
Key Selections
-107 Model Number.
Copy Function
Setting
Factory
Range
Setting
1 ~ 94
2
1 ~ 94
91
0 ~ 1
1
0 ~ 1
1
0 ~ 2
0
kVA
0 ~ FF
Dependent
0 ~ 1
0
0 ~ 1
1
0 ~
0 hr
65535 hr
0 ~ 1
1
0 ~
0 hr
65535 hr
0 ~ 1
0
0 ~ 1
0
0 ~ 3
0
0 ~ 1
0
YASKAWA TM.iQp.10 Technical Manual Supplement
Menu
Location
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming