YASKAWA iQpump Manual Supplement page 6

Intelligent pump controller
Table of Contents

Advertisement

2 General Safety
2
General Safety
Important note when replacing an iQpump Controller.
Verify software ID drive monitor U1-14 when replacing an iQpump Controller in a multiplex network configuration.
Set parameter P9-99 to a value of 0 : "A-version 30034" if (ONE or MORE) iQpump Controllers on the network have
software version monitor U1-14=30034 and nameplate PRG: 0034. Otherwise do not change P9-99 setting from factory
default. Failure to comply will result abnormal drive operation.
Supplemental Safety Information
Read and understand this manual and the iQpump Controller User Manual before installing, operating, or servicing this
option unit. The drive must be installed according to the iQpump Controller User Manual and local codes. Observe all
cautions and warnings in this document and the standard drive manuals.
Refer to the iQpump Controller Simplex Cheat Sheet TM.iQp.04 and the iQpump Controller User Manual TM.iQp.06 for
safety information and installation and start-up instructions.
This document is a supplement to the standard iQpump Controller Manuals. It describes the enhanced functionality of
drive software version U1-14=30035 and nameplate PRG: 0035 or greater.
• Custom software is provided to add functionality to a standard AC drive to enhance or enable use in a specific
application.
6
NOTICE
Abnormal Pump Operation Hazard
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement