5 Feature Details - Remote Drive Disable
Figure 2
Active
Inactive
P4-25 Remote Drive Disable On-Delay Time
Range
Sets the amount of time a "Remote Drive Disable" condition needs to be
1 - 1000 sec
present before the drive will stop.
P4-26 Remote Drive Disable Off-Delay Time
Range
Sets the amount of time a "Remote Drive Disable" condition must be absent
1 - 1000 sec
before the drive will be allowed to run.
Multi-function Input Setting: Remote Drive Disable Function
Setting
Remote Drive Disable: Prevents the iQpump Controller from running when active for the time set in
72 Remote Drv Disbl
P4-25. Must be inactive for the time set in P4-26 to allow the drive to run again.
Note: Parameter P4-24 determines if this input is Normally Open or Normally Closed.
Alarm: Remote Drive Disable
Alarm Display
Multi-function Input Terminal S
R-DNE-Sx
or
Remote Drv Dis
Multi-function Input Terminal S
Note: S
or Sx denotes the digital input terminal programmed for this function.
12
P4-26 Off-Delay Time
Remote
Drive Disable
iQpump Drive Stopped
Figure 2 Remote Disable: Active to Inactive Operation
iQpump Drive Enabled
Description
Description
Description
Description
(H1-0
= 72) has been closed for the time set in P4-25 when P4-24 = 0.
(H1-0
= 72) has been open for the time set in P4-25 when P4-24 = 1.
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
Time
Default
0 sec
Default
0 sec