Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Communication Parity
H5-03
0427
Selection
Serial Com Sel
Stopping Method after
H5-04
0428
Communication Error
Serial Flt Sel
Communication Error
H5-05
0429
Detection Selection
Serial Flt Dtct
Drive Transmit Wait Time
H5-06
042A
Transmit WaitTim
RTS Control Selection
H5-07
042B
RTS Control Sel
Communication Protocol
H5-08
042C
Selection
Com Protocol Sel
Communication Error
H5-09
0435
Detection Time
CE Detect Time
Motor Overload Protection
L1-01
0480
Selection
MOL Flt Sel
Motor Overload Protection
L1-02
0481
Time
MOL Time Const
Motor Overheat Alarm
L1-03
0482
Operation Selection
Mtr OH Alarm Sel
Motor Overheat Fault
L1-04
0483
Operation Selection
Mtr OH Fault Sel
Motor Temperature Input
L1-05
0484
Filter Time
Mtr Temp Filter
YASKAWA TM.iQp.10 Technical Manual Supplement
Display
Selects the communication parity for Terminals R+, R-, S+ and S-.
0: No Parity
1: Even Parity
2: Odd Parity
Note: Drive power must be cycled before the changes will take effect.
<0034>
Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a communications
fault.
1: Enabled - If communications are lost for more than the time specified in
parameter H5-09, a communications fault will occur.
Sets the time from when the drive receives data to when the drive sends
data.
Enables or disables "request to send" (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
0: MEMOBUS/Modbus
1: N2 (Metasys)
2: FLN (APOGEE)
Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-04.
Enables or disables the motor thermal overload protection.
0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor
Determines how much time will elapse prior to a motor overload fault
(OL1), when motor amps exceed the value set in parameter E2-01 by
10 %. Actual (OL1) trip time will vary depending on severity of overload.
Operation selection when the motor temperature analog input
(H3-09 = E) exceeds the OH3 alarm level (1.17 V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Stopping method when the motor temperature analog input
(H3-09 = E) exceeds the OH4 level (2.34 V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
Delay Time applied to motor temperature analog input (H3-09 = E) for
filtering purposes.
Description
Motor Overload
Setting
Factory
Menu
Range
Setting
Location
0 ~ 2
0
Programming
0 ~ 3
3
Programming
0 ~ 1
1
Programming
5 ~ 65 ms
5 ms
Programming
0 ~ 1
1
Programming
0 ~ 2
0
Programming
0.0 ~
2.0 sec
Programming
10.0 sec
0 ~ 1
1
Programming
0.1 ~
8.0 min
Programming
20.0 min
0 ~ 3
3
Programming
0 ~ 2
1
Programming
0.00 ~
0.20 sec
Programming
10.00 sec
65