YASKAWA iQpump Manual Supplement page 57

Intelligent pump controller
Table of Contents

Advertisement

Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Maximum Output
E1-04
0303
Frequency
Max Frequency
Maximum Output Voltage
E1-05
0304
Max Voltage
Base Frequency
E1-06
0305
Base Frequency
Mid Output Frequency A
E1-07
0306
Mid Frequency A
Mid Output Voltage A
E1-08
0307
Mid Voltage A
Minimum Output
E1-09
0308
Frequency
Min Frequency
Mid Output Voltage
E1-10
0309
Min Voltage
Mid Output Frequency B
E1-11
030A
Mid Frequency B
Mid Output Voltage B
E1-12
030B
Mid Voltage B
Base Voltage
E1-13
030C
Base Voltage
Motor Rated Current
E2-01
030E
Motor Rated FLA
E2-03
030F
No-Load Current
Number of Motor Poles
E2-04
0311
Number of Poles
Motor Line-to-Line
E2-05
0312
Resistance
Term Resistance
Operation Selection after
F6-01
03A2
Communication Error
Com Bus Flt Sel
Input Level of External
Fault from
F6-02
03A3
Communication Option
Card
EF0 Detection
Stopping Method for
External Fault from
F6-03
03A4
Communication Option
Card
EF0 Fault Action
Current Monitor Display
F6-05
03A6
Unit Selection
Current Unit Sel
YASKAWA TM.iQp.10 Technical Manual Supplement
Display
Output voltage (V)
To set V/f characteristics in a straight line, set the same values for E1-07
and E1-09. In this case, the setting for E1-08 will be disregarded.
Always ensure that the four frequencies are set in the following manner:
E1-04 (FMAX)
Set only when V/f is finely adjusted at rated output range.
Adjustment is not normally required.
Set to the motor nameplate full load amps.
Sets the magnetizing current of the motor.
Set to the number of poles. Used for no-flow detection function and for the
calculation of rpm related parameters.
Phase to phase motor resistance, normally set by the autotuning routine.
Sets the stopping method for option PCB communications error (BUS
fault). Active only when a communications option PCB is installed and
when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Always detected
1: Detected only during run
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: A Display
1: 100 % /8192 (Drive Rated Current)
Description
VMAX
(E1-05)
VBASE
(E1-13)
VA
(E1-08)
VMIN
(E1-10)
FMIN
FA
FBASE FMAX
(E1-09) (E1-07) (E1-06) (E1-04)
Frequency (Hz)
E1-06 (FA) > E1-07 (FB)
E1-09 (FMIN)
Motor Setup
Communication Option Setup
Setting
Factory
Menu
Range
Setting
Location
0.0 ~
60.0 Hz
Programming
120.0 Hz
0.0 ~ 255.0
230.0 V
(240V)
Programming
0.0 to 510.0
460.0 V
(480V)
0.0 ~
60.0 Hz
Programming
200.0 Hz
0.0 ~
3.0 Hz
Programming
200.0 Hz
0.0 ~ 255.0
(240V)
17.2 Vac
Programming
0.0 to 510.0
34.5 Vac
(480V)
0.0 ~
1.5 Hz
Programming
200.0 Hz
0.0 ~ 255.0
(240V)
10.3 Vac
Programming
0.0 to 510.0
20.7 Vac
(480V)
0.0 ~
0.0 Hz
Programming
200.0 Hz
0.0 ~ 255.0
(240V)
0.0 Vac
Programming
0.0 to 510.0
(480V)
0.0 ~ 255.0
(240V)
0.0 Vac
Programming
0.0 to 510.0
(480V)
10 ~
kVA
Pump Quick
200 %
Dependent
Setup
kVA
kVA
Programming
Dependent
Dependent
Pump Quick
2 ~ 48
2
Setup
0.000 ~
kVA
Programming
65.000
Dependent
0 ~ 3
1
Programming
0 ~ 1
0
Programming
0 ~ 3
1
Programming
0 ~ 1
0
Programming
57