Parameter Name
Parameter
Addr.
Digital Operator
No.
Hex
Terminal S7 Function
H1-05
0404
Selection
Terminal S7 Sel
H1-12
External Fault 3 Delay
87A
Time
EF3 Delay Time
<0034>
H1-13
External Fault 4 Delay
87B
Time
EF4 Delay Time
<0034>
H1-14
External Fault 5 Delay
87C
Time
EF5 Delay Time
<0034>
H1-15
External Fault 6 Delay
87D
Time
EF6 Delay Time
<0034>
H1-16
External Fault 7 Delay
87E
Time
EF7 Delay Time
<0034>
Denotes that parameter can be changed when the drive is running.
60
Display
83: Thermostat Fault,
Function Active in Auto Mode.
Closed: Drive will trip on "Thermostat Fault".
Open: Thermostat fault not active.
Open: Low Water Level Fault.
84: Pre-charge
Closed: Disables pre-charge function.
Open: Pre-charge function enabled.
85: Low Water Level
Function Active in Auto Mode during normal operation, also used with
pre-charge function.
Function logic depends on parameter P1-15 (Water DI Config).
P1-15 = 0, or 2 (Normally open).
Closed: Low Water Level Fault.
Open: Reservoir/Tank is filled to normal level.
P1-15 = 1 or 3 (Normally Closed).
Closed: Reservoir/Tank is filled to normal level.
Pre-charge function: Function uses low water level input as "Tank/
Reservoir" feedback to indicate water level reached.
IMPORTANT
Program P1-15 to 0 or 2 when the "Low Water" function is not used. 86:
Fixed Speed Auto
Function Active in Auto Mode Only, Pre-charge and Thrust Bearing
function have a higher priority. When fixed speed auto is active (closed)
drive disabled Sleep Mode and Lead/Lag operation.
Closed: Drive runs at P3-02 frequency, PI Control disabled
Open: Drive runs normal operation auto mode.
87: Thermostat Fault, Normally Closed
Function Active in Auto Mode.
Closed: Thermostat fault not active.
Open: Drive will trip on "Thermostat Fault".
Sets the amount of time delay applied to the EF3 fault.
(20 ≤ H1-01 ≤ 2F)
Sets the amount of time delay applied to the EF4 fault.
(20 ≤ H1-02 ≤ 2F)
Sets the amount of time delay applied to the EF5 fault.
(20 ≤ H1-03 ≤ 2F)
Sets the amount of time delay applied to the EF6 fault.
(20 ≤ H1-04 ≤ 2F)
Sets the amount of time delay applied to the EF7 fault.
(20 ≤ H1-05 ≤ 2F)
Description
<0034>
<0032>
Setting
Factory
Range
Setting
0 ~ 87
84
0.00 ~
0.00 sec
300.00 sec
0.00 ~
0.00 sec
300.00 sec
0.00 ~
0.00 sec
300.00 sec
0.00 ~
0.00 sec
300.00 sec
0.00 ~
0.00 sec
300.00 sec
YASKAWA TM.iQp.10 Technical Manual Supplement
Menu
Location
Programming
Programming
Programming
Programming
Programming
Programming