YASKAWA iQpump Manual Supplement page 89

Intelligent pump controller
Table of Contents

Advertisement

Addr.
Parameter No.
Hex
U1-91
0721
U1-92
0722
U1-93
723
U1-94
724
U1-95
725
U1-96
72A
U1-97
72B
Applies when P8-01 = 0 or 1
Applies when P8-01 = 2
U1-98
72C
U1-98
72C
<0035>
U1-99
72D
YASKAWA TM.iQp.10 Technical Manual Supplement
Parameter Name Digital
Operator Display
Pump Feedback
Pump Feedback
Pump Status
Pump Status
Total Set-point Compensation
Total SP Comp.
Motor Speed
Motor Speed
Flow Rate
Flow Rate
Volume Accumulated
(fine)
Volume (fine)
Volume Accumulated
(course)
Volume (course)
Water Level
Water Level
Water Level
Suction Pressure
Anti-No-Flow Timer
ANF Timer
Displays scaled feedback.
Resolution 0.1
Display pump running status.
0 0 0 0 0 0 0 0
Displays total absolute setpoint compensation.
Resolution 1.
Displays motor speed (rpm).
Used for no-flow detection (P2 Group).
Displays the flow rate, based upon the voltage present on Terminal A1 and parameters P6-01
and P6-02. A two second 1st order filter will be applied to this monitor.
Displays the volume that has been measured by Terminal A1. Total volume can be calculated
as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.
Displays the volume that has been measured by Terminal A1. Total volume can be calculated
as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.
Displays the amount of water above the water level sensor.
Displays the amount of suction pressure.
When this value reaches the P2-24 setting, the Anti-No-Flow feature begins to reduce the
output frequency.
Description
Monitor
1: Drive (Pump 1)
1: Pump 2 on
1: Pump 3 on
Not used. Always 0.
89