Smartgen HGM6000K Series Operating Manual page 15

Automatic generator module
Table of Contents

Advertisement

Pin
Function
Magnetic
15
+ve
Magnetic
16
-ve
Temp.
17
input
18
Oil pressure input
19
Liquid level input
20
Auxiliary input 1
21
Auxiliary input 2
22
Remote start input
CT secondary for
23
A
CT secondary for
24
B
CT secondary for
25
C
CT
secondary
26
common
Gens A voltage
27
monitoring
Gens B voltage
28
monitoring
Gens C voltage
29
monitoring
30
Gens neutral input 1.0mm Connect to Genset neutral terminal.
Mains A voltage
31
monitoring
Mains B voltage
32
monitoring
Mains C voltage
33
monitoring
Mains neutral
34
input
RS485 port
35
common GND
36
RS485 port A(-)
37
RS485 port B(+)
38
Auxiliary input 4
39
Auxiliary input 5
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
Dim
pickup
Connect to Magnetic Pickup device
pickup
Connecting
sensor
temperature resistance type
sensor.
Connect
sensor.
Connect to liquid level sensor.
1.0mm Switch to -ve
1.0mm Switch to -ve
1.0mm Switch to -ve
1.5mm
1.5mm
1.5mm
1.5mm See also back install instructions.
1.0mm
1.0mm
1.0mm
1.0mm
1.0mm
1.0mm
1.0mm Connect to mains neutral terminal.
0.5mm
0.5mm
0.5mm
1.0mm Switch to -ve
1.0mm Switch to -ve
Description
water/cylinder
to
oil
pressure
Connect to secondary of A monitoring
CT
Connect to secondary of B monitoring
CT
Connect to secondary of C monitoring
CT.
Connect to Genset A output
(Recommend 2A fuse)
Connect to Genset B output
(Recommend 2A fuse)
Connect to Genset C output
(Recommend 2A fuse)
Connect to mains A output.
(Recommend 2A fuse)
Connect to mains B output.
(Recommend 2A fuse)
Connect to mains C output.
(Recommend 2A fuse)
Use only 120Ω RS485 approved cable.
ISSUE 2011-06-20
Version 1.7
Reference
table 4
Reference
table 3
Page 16 of 34