Smartgen HGM6000K Series Operating Manual page 18

Automatic generator module
Table of Contents

Advertisement

Num
Parameter
P 18
Fail
to
stop
(P13)
delay
P 19
ATS
close
(P14)
time
P 20
Flywheel teeth (10-300)
(P15)
Gens
P 21
abnormal
(P16)
delay
P 22
Gens over volt
(P17)
shutdown
Gens
under
P 23
volt
(P18)
shutdown
P 24
Under speed
(P19)
shutdown
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
Range
(0-120)s
(0-10)s
(0-20.0)s
(30-360)V
(30-360)V
(0-6000)RPM
Default
When
shutdown output time" for
zero, idle time delay stop
steady to time, and when
0
"ETS solenoid hold output
time" is not equal to zero,
from
shutdown delay end to stop
steady need of time.
Mains or Genset switch
closing pulse width, when it
5.0
is
continuous.
The
engine starter teeth, used
for
118
condition
engine speed detection, see
behind
instructions.
Too high or too low voltage
10.0
genset alarm delay.
When genset voltage is
over than the point, genset
over shutdown voltage is
264
active. When the point is
360V, genset over voltage is
disabled.
When genset voltage is
under than the point, genset
under shutdown voltage is
196
active. When the point is
30V, genset under voltage
is disabled.
When the engine speed is
under than the point and
1200
hold great than 10 seconds,
genset
speed is active.
ISSUE 2011-06-20
Version 1.7
Remark
"ETS
solenoid
ETS
solenoid
zero,
output
flywheel
teeth
starters
separation
judgment
and
the
installation
under
shutdown
Page 19 of 34