Smartgen HGM6000K Series Operating Manual page 17

Automatic generator module
Table of Contents

Advertisement

Num
Parameter
P 08
Number
(P03)
Crank
P 09
Preheat time
(P04)
P 10
Cranking time
(P05)
P 11
Crank interval
(P06)
time
P 12
Safe run time
(P07)
P 13
Start idle time
(P08)
P 14
Warming
(P09)
time
P 15
Cooling time
(P10)
P 16
Stop idle time
(P11)
P 17
ETS solenoid
(P12)
hold
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
Range
of
(1-10)Times
(0-300)s
(3-60)s
(3-60)s
(1-60)s
(0-3600)s
up
(3-3600)s
(3-3600)s
(0-3600)s
(0-120)s
Default
When
success, most of cranking
numbers.
3
setting
controller send out start fail
signal.
Before the starter adds the
0
electricity, preheat plug add
to the electricity in advance.
The starter adds the time of
8
the electricity each time.
When the engine start not
successful, in the second
10
plus electric before the start
of the waiting time.
At
this
pressure,
temperature, under speed,
under
10
voltage and charging failure
and
(configured) alarm is void
volume.
Start genset idle running
0
time.
Genset entered high speed
10
operation, in the warm-up
before closed for time.
After unloading in genset,
10
the time needed to cool
before shutdown.
When stop idling genset
0
running time.
It‟s the delay for energizing
20
to stop.
ISSUE 2011-06-20
Version 1.7
Remark
engine
start
no
When
reach
crank
numbers,
time,
low
oil
high
water
frequency,
under
auxiliary
input
Page 18 of 34

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm6010kHgm6010kcHgm6020kHgm6020kc

Table of Contents