3 SPECIFICATION
Operating Voltage
Power Consumption
Alternator Input Range
3-Phase 4 Wire
2-Phase 3 Wire
Single phase 2 Wire
Frequency
Magnetic AC voltage
Magnetic AC Frequency
Start Relay Output
Fuel Relay Output
Auxiliary Relay Output (1-4)
Overall Dimensions
Panel cutoff
Operating Temp. Range
Storage Condition
Protective Level
Insulation Intensity
C. T. Secondary
Weight
4 OPERATION
4.1 KEY FUNCTION
Stop/ Reset
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
DC8.0V to 35.0V, Continuous
<3W(Standby mode: ≤2W)
15VAC - 360VAC (ph-N)
15VAC - 360VAC (ph-N)
15VAC - 360VAC (ph-N)
50Hz - 60Hz
1.0V to 24V (effective value)
10,000 Hz (max)
16 Amp DC28V at supply voltage.
16 Amp DC28V at supply voltage.
(1) 7Amp DC28V at supply voltage,
(2)7Amp 250VAC free voltage contact,
(3, 4)16Amp 250VAC free voltage contact.
209mm x 153mm x 55mm
186mm x 141mm
Temperature: (-25~+70)º C Humidity: (20~90)%
Temperature: (-30~80)º C
IP55: when waterproof rubber ring added between
controller and its panel.
IP42: when waterproof rubber ring not have
between controller and its panel.
Object: among in input/output/power
Quote standard: IEC688-1992
Test way: AC1.5 kV / 1min 3mA leakage current
5A (rated )
0.69kg
Can stop genset under mode of Manual/Auto;
Can reset alarming under Stop;
To test panel indicators are OK or not, pressing this
ISSUE 2011-06-20
Version 1.7
Page 6 of 34