Smartgen HGM6000K Series Operating Manual page 21

Automatic generator module
Table of Contents

Advertisement

Num
Parameter
P 40
Battery under
(P35)
volt
High
P 41
temperature
(P36)
warn
Low
P 42
pressure
(P37)
warn
P 43
CT rate
(P38)
P 44
Full
load
(P39)
current
Over current
P 45
shutdown
(P40)
percentage
Over current
P 46
shutdown
(P41)
delay
Over
current
P 47
warn
(P42)
percentage
Switching
P 48
value output1
(P43)
set
Switching
P 49
value output 2
(P44)
set
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
Range
(4-30)V
(80-140)º C
oil
(0-400)kPa
(5-6000)/5
(5-6000)A
(50-130)%
(0-3600)s
(50-130)%
(0-11)
(0-11)
Default
When
voltage is less than the
point
8.0
seconds,
voltage signal is active. It‟s
a warning alarm.
When engine temperature
sensor value is large than
this point, send out warning
95
alarm. When the value is
140,
alarm. (It‟s suited for engine
temperature sensor only).
When engine oil pressure
sensor value is less than
this point send out warning
124
alarm. When the value is
zero,
alarm. (It‟s suited for oil
pressure sensor only)
500
Current transformer rate
Mains
500
maximum rated current.
When the load current is
120
over than the point, the over
current delay is initiated.
When load current is over
than the point and hold
great than the timer, send
1296
out over current signal.
When the delay is zero,
over current is disabled.
When the load current is
110
over than the point, over
current warn icon illume.
2
ETS solenoid to stop
3
Idle control
ISSUE 2011-06-20
Version 1.7
Remark
genset
battery
and
hold
for
battery
under
send
out
warning
send out
warning
or
genset
set
Page 22 of 34