has fallen below the low oil pressure setting level after the Safety On timer has
expired and the input of Inhibit OPL stop is activated, a warning will occur. At the
same time LCD screen
icon lighten.
LOSS OF SPEED SIGNAL WARN, if the speed sensing signal is lost, a warning
will occur and the lost speed delay set to zero, a warning will occur. At the same
time LCD screen
icon lighten.
GENSET OVER CURRENT WARN, if the module detects a genset output current
in excess of the setting and the over current delay set to zero, a warning is
initiated. At the same time LCD screen
icon lighten.
FAIL TO STOP WARN, if the module detects the engine is still running when the
„Fail to stop timer‟ expires, a warning is initiated. At the same time LCD screen
icon lighten.
START BATTERY OVER VOLTAGE WARN, if the module detects that the plant
DC supply has risen above the high volts setting level, a warning is initiated. At the
same time LCD screen
icon lighten.
START BATTERY UNDER VOLTAGE WARN, if the module detects that the plant
DC supply has fallen below the low volts setting level, a warning is initiated. At the
same time LCD screen
icon lighten.
LOW FUEL LEVEL WARN, if the module detects that the engine oil level has
fallen below the low level setting level has expired, a warning will occur. At the
same time LCD screen
icon lighten.
FAILED TO CHARGE WARN, if the module detects that the charge of volts has
fallen below the setting level has expired, a warning will occur. At the same time
LCD screen
icon lighten.
GENSET OVER VOLTAGE WARN, if the module detects a genset output voltage
in excess of the setting a warning is initiated. At the same time LCD screen
icon lighten.
GENSET UNDER VOLTAGE WARN, if the module detects a genset output voltage
below the setting a warning is initiated. At the same time LCD screen
icon
lighten.
OVER SPEED WARN, if the engine speed exceeds the setting value a warning is
initiated. At the same time LCD screen
icon lighten.
UNDER SPEED WARN, if the engine speed falls below the setting value after the
Safety On timer has expired, a warning is initiated. At the same time LCD screen