Num
Parameter
P 32
Gens over volt
(P27)
warn
P 33
Gens
under
(P28)
volt warn
P 34
Under speed
(P29)
warn
P 35
Over
speed
(P30)
warn
P 36
Gens
under
(P31)
freq warn
P 37
Gens
over
(P32)
freq warn
P 38
Charge
(P33)
volt
P 39
Battery
over
(P34)
volt
HGM6000K Series Automatic Generator Module
HGM6000K Series Automatic Generator Module
Range
(30-360)V
(30-360)V
(0-6000)RPM
(0-6000)RPM
(0-75.0)Hz
(0-75.0)Hz
fail
(0-30)V
(12-40)V
Default
When genset voltage is
over than the point, genset
over warning voltage is
256
active. When the point is
360V, genset over voltage is
disabled.
When genset voltage is
under than the point, genset
under warning voltage is
205
active. When the point is
30V, genset under voltage
is disabled.
When the engine speed is
under than the point, genset
1350
under warning speed is
active.
When the engine speed is
over than the point, genset
1650
over
active.
When genset frequency is
low than the point, genset
47.0
under warning frequency is
active.
When genset frequency is
over than the point, genset
55.0
over warning frequency is
active.
During genset is running,
when
WL/D+ voltage is low than
6.0
this point and remain for 5
seconds,
warning alarm.
When
voltage is over than the
point
33.0
seconds,
voltage signal is active. It‟s
a warning alarm.
ISSUE 2011-06-20
Version 1.7
Remark
warning
speed
charge
alternator
genset
will
genset
battery
and
hold
for
20
battery
over
Page 21 of 34