Device parameters and interfaces
Note!
With this module, the settings for the Preset (module 3), Offset (module 5) and Scaling
(module 6) modules must be taken into account.
8.1.7.18 Module 17: Dynamic position limit value 2
Description
The limit value function compares the position value with a stored position. If the value is
above or below the limit value, the limit value status 2 in module 12 is set and, if configured,
the switching output is appropriately set.
The limit value is transferred to the BPS 34 together with the output data of this module by
the PROFIBUS master.
Parameters
Parameter
a
Parameter activates the limit
Limit value
value check.
mode 2
b
Condition for the signal change
Switching
of the switching output/status bit.
type 2
c
Relative offset of the switching
Hysteresis
point.
2 in [mm]
Parameter length: 4 byte
Hex coding of module 17 "Dynamic position limit value 2"
The value listed in the table shows the hex coding of the default settings.
10
Input data
None
76
Description
addr.
00
00
Rel.
Data
Value range
type
unsign
0: Off
0
8
1: On
unsign
0: Value greater than limit
1
8
1: Value less than limit
unsign
2
0 ... 65,535
16
00 00
BPS 34
Default
Unit
CR to
module
0
7g
8d
0
12f
0
mm
Leuze electronic