Leuze electronic BPS 34 Operating Instructions Manual page 75

Bar code positioning system profibus dp
Hide thumbs Also See for BPS 34:
Table of Contents

Advertisement

Device parameters and interfaces
8.1.7.16 Module 15: Static position limit value 2
Description
The limit value function compares the output position value with a position stored during
configuration. If the value is above or below the limit value, the limit value status 2
(module 12) is set and, if configured, the switching output (module 8) is appropriately set.
Parameters
Parameter
a
Parameter activates the limit
Limit value
value check.
mode 2
b
Condition for the signal change
Switching
of the switching output/status bit.
type 2
c
Relative offset of the switching
Hysteresis
point
2 in [mm]
d
Limit value is compared to the
Limit value
current position value.
2 in [mm]
Parameter length: 8 byte
Hex coding of module 15 "Static position limit value 2"
The value listed in the table shows the hex coding of the default settings.
0E
Input data
None
Output data
None
Note!
With this module, the settings for the Preset (module 3), Offset (module 5) and Scaling
(module 6) modules must be taken into account.
74
Description
addr.
00
00
Rel.
Data
Value range
type
unsign
0: Off
0
8
1: On
unsign
0: Value greater than limit
1
8
1: Value less than limit
unsign
2
0 ... 65,535
16
4
sign32 -10,000,000 ... 10,000,000
00 00
00 00 00 00
BPS 34
Default
Unit
CR to
module
0
7g
0
8d
0
mm
0
mm
12f
Leuze electronic