Advertisement

8.1.7.17 Module 16: Dynamic position limit value 1
Description
The limit value function compares the position value with a stored position. If the value is
above or below the limit value, the limit value status 1 in module 12 is set and, if configured,
the switching output is appropriately set.
The limit value is transferred to the BPS 34 together with the output data of this module by
the PROFIBUS master.
Parameters
Parameter
a
Parameter activates the limit
Limit value
value check.
mode 1
b
Condition for the signal change
Switching
of the switching output/status bit.
type 1
c
Relative offset of the switching
Hysteresis
point.
1 in [mm]
Parameter length: 4 byte
Hex coding of module 16 "Dynamic position limit value 1"
The value listed in the table shows the hex coding of the default settings.
0 F
Input data
None
Output data
Output
data
d
Limit value is compared to the
Limit value
current position value.
1 in [mm]
Output data length: 4 byte
Leuze electronic
Description
addr.
00
00
Description
addr.
Device parameters and interfaces
Rel.
Data
Value range
type
unsign
0: Off
0
8
1: On
unsign
0: Value greater than limit
1
8
1: Value less than limit
unsign
2
0 ... 65,535
16
00 00
Rel.
Data
Value range
type
0
sign32 -10,000,000 ... 10,000,000
BPS 34
Default
Unit
CR to
module
0
7g
8d
0
12e
0
mm
Default
Unit
CR to
module
0
mm
75