13 Application Parameters by Industry

Industry-Specific Parameter Application
13-00
Settings
 NOTE: after you select the macro, some of the default values adjust automatically according to
the application selection.
 Group setting 02: Compressor (IM)
The following table lists the relevant compressor application parameters.
Pr.
00-11
Speed Control Mode
00-16
Duty Selection
00-17
Carrier Frequency
Master Frequency Command Source
00-20
(AUTO) / Source Selection of the PID
Target
00-21
Operation Command Source (AUTO)
00-22
Stop Method
00-23
Control of Motor Direction
01-00
Maximum Operation Frequency
01-01
Motor 1 Rated / Base Frequency
01-02
Motor 1 Rated / Base Output Voltage
01-03
Motor 1 Mid-Point Frequency 1
01-04
Motor 1 Mid-Point Voltage 1
01-05
Motor 1 Mid-Point Frequency 2
01-06
Motor 1 Mid-Point Voltage 2
01-07
Motor 1 Minimum Output Frequency
01-08
Motor 1 Minimum Output Voltage
01-11
Output Frequency Lower Limit
01-12
Acceleration Time 1
01-13
Deceleration Time 1
03-00
Analog Input Selection (AVI)
03-01
Analog Input Selection (ACI)
05-01
Full-Load Current For Induction Motor 1 (A)
05-03
Rated Speed for Induction Motor 1 (Rpm)
05-04
Number of Poles for Induction Motor 1
0: Disabled
1: User-defined Parameter
2: Compressor (IM)
3: Fan
4: Pump
10: Air Handling Unit, AHU
Explanation
Chapter 12 Descriptions of Parameter SettingsC2000 Plus
(appied to 230V / 460V models)
 You can set this parameter during operation
Default: 0
0 (V/F control)
0 (Normal load)
Default setting
2 (External analog input)
1 (External terminals)
0 (Ramp to stop)
1 (Disable reverse)
Default setting
Default setting
Default setting
Default setting
Default setting
Default setting
Default setting
Default setting
Default setting
20 (Hz)
20 (s)
20 (s)
0 (No function)
1 (Frequency command)
Default setting
Default setting
Default setting
12.1-13-1