Ups System Power Wiring Preparations - Eaton 93E G2 100/100 User And Installation Manual

Table of Contents

Advertisement

Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
If battery systems are located in the same room as the UPS, the
environmental requirements of the battery manufacturer must be followed, if
they are more stringent than the UPS requirements. Operating temperatures
above the recommended range will result in decreased battery life and
performance, and may reduce or void the battery warranty.
Table 8: Air conditioning or ventilation requirements during full load operation
Model
Eaton 93E G2 100/100
Eaton 93E G2 120/120
Eaton 93E G2 200/160
Eaton 93E G2 200/200
4.3.2
The UPS system installation must meet the following guidelines:
The system must be installed on a level, non-combustible floor suitable for
computer or electronic equipment.
The system must be installed in a temperature and humidity controlled
indoor area free of conductive contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements
shown in Table
dimensions are in millimeters.
HIGH TOUCH CURRENT. EARTH CONNECTION ESSENTIAL BEFORE
CONNECTING SUPPLY. As a result of the connected loads high leakage
current is possible. Connection of the earth (ground) is required for proper
product operation. Do not check UPS operation by removal of the Earth
(ground) connection.
©
Eaton Corporation plc 2019. All rights reserved.
Rating
100 kVA
120 kVA
160 kVA
200 kVA

UPS system power wiring preparations

6
, and the size requirements shown in Figure
CAUTION
Input/output
voltage
380/380 VAC
400/400 VAC
415/415 VAC
380/380 VAC
400/400 VAC
415/415 VAC
380/380 VAC
400/400 VAC
415/415 VAC
380/380 VAC
400/400 VAC
415/415 VAC
WARNING
Revision: 002
Document ID: P-164000848
User's and installation guide
Heat rejection
BTU/hr x1000 (kg-cal/hr)
23.11 (5826)
27.74 (6991)
36.99 (9322)
46.23 (11651)
7
. The
41 (118)

Advertisement

Table of Contents
loading

This manual is also suitable for:

93e g2 120/12093e g2 200/16093e g2 200/200