Ups Environmental Specifications - Eaton 93E G2 100/100 User And Installation Manual

Table of Contents

Advertisement

Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
Item
Load power factor (rated)
Overload capability in double conversion
(normal) mode
Overload capability in the stored energy
mode
Overload capability in the bypass mode
Output current limitation, short circuit capa-
bility (rms)
9.4
Table 27: UPS environmental specifications
Item
Operating temperature
Operating altitude
Storage temperature
Relative humidity (operating and storage)
Pollution degree
Protective class
IP class
Earthing systems
Electrical (overvoltage category)
Acoustical noise
EMC
©
Eaton Corporation plc 2019. All rights reserved.

UPS environmental specifications

Value
nominal 0.9
≤ 125% for 10 minutes
≤ 150% for 1 minute
≥ 150% for 500 milliseconds
102 - 125% for 1 minute
126 - 150% for 30 seconds
> 150% for 150 milliseconds
< 115% continuous of nominal line current
Transient 10 x peak current for 20 millisec-
onds
100 kVA UPS: 350 A
120 kVA UPS: 440 A
160 kVA UPS: 720 A
200 kVA UPS: 720 A
Value
0 to 40 °C without derating. The recom-
mended operating temperature is 20 to 25
°C.
1000 m without derating, up to 2000 m with
derating
- 25 to 55 °C, excluding batteries (pro-
longed storage above 40 °C causes rapid
battery selfdischarge)
5% to 95% maximum noncondensing, rec-
ommended range* 20% to 60%
min PD2
Protective class I
IP20
TN-s, TN-C, or TN-C-S
OVCIII
≤ 62 dB (100-120kVA) and 70 dB (160-200
kVA) at a 1 m distance, at 75% load, per
ISO 7779
IEC 62040-2 ed.3 C3
Revision: 002
Document ID: P-164000848
User's and installation guide
109 (118)