Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
Figure 28. Remote EPO (REPO) terminal block connector assignments
Table 16: Remote EPO connections
Remote EPO
terminal
1
2
3
4
4.
Route the remote EPO wiring to the terminal block, see Figure
5.
Connect the wiring as shown in Table
remote EPO or Table
6.
If you are using a normally-closed remote EPO switch, connect a jumper
wire between pins 3 and 4 on the remote EPO terminal block.
7.
If you are installing multiple remote EPO switches, wire the additional
switches in parallel with the first remote EPO.
8.
If required, install wiring from the remote EPO switch to the trip circuitry of
the upstream protective devices. A second contact block is provided on the
©
Eaton Corporation plc 2019. All rights reserved.
Description
Input: a normally-closed dry contact used to activate UPS EPO
from a remote switch.
Input: a normally-open dry contact used to activate UPS EPO
from a remote switch.
18
30
and Figure
Revision: 002
User's and installation guide
17
29
and Figure
for a normally-open
for a normally-closed remote EPO.
Document ID: P-164000848
22
.
69 (118)