Contents 1. INTRODUCTION 1.1 S AFETY INSTRUCTION 1.2 C ERTIFICATION TANDARDS 1.3 S PECIAL YMBOLS 2.PRESENTATION 2.1 M ODEL 2.2 E LECTRICAL STRUCTURE 2.2 UPS VIEWS 3.INSTALLATION 3.1 U NPACKING 3.2 P ACKAGE CONTENT 3.3 C ONNECTION 4.OPERATION 4.1 D ISPLAY AND UTTONS 4.2 O...
1. Introduction 1.1 Safety instruction • The UPS must be installed and maintained exclusively by quailified staff. See installation and operation instructions before connecting to the supply. • The UPS must be installed with an earth connection. It has a high leakage current. The first wire to be connected is the earth wire, which must be connected to the terminal marked PE (yellow/green).
230V (220/240) 9E20Ki 20kVA/16kW Combo 230V (220/240) 9E20KiXL 20kVA/16kW Combo 230V (220/240) 9EEBM180 For 9E6Ki 180V 9EEBM240 For 9E10Ki, 9E10KiXL 240V “XL” Model: Model with internal supercharger, and without internal batteries. Other models with internal batteries 2.2 Electrical structure 9E6Ki...
Main power wiring Bypass Input Switch Maintain Switch Input Output AC-DC DC-AC INPUT filter filter Output OUTPUT Switch Internal Charger power Battery 2.2 UPS views 2.2.1 UPS F RONT VIEW ① Display ② Multipurpose buttons ③ Wheels (front wheels swivel and can be locked, fixed rear wheels) Page 6...
Page 7
2.2.2 UPS R EAR VIEW 9E6Ki 9E6Ki With backpanel cover Without backpanel cover 9E10Ki/9E10KiXL 9E10Ki/9E10KiXL With backpanel cover Without backpanel cover ④ ⑩ USB communication port Input switch ⑤ ⑪ RS232 communication port and contacts Cover for terminals ⑥ ⑫...
Page 8
UPS R EAR VIEW 9E15Ki/9E15KiXL/9E20Ki/9E20KiXL 9E15Ki/9E15KiXL/9E20Ki/9E20KiXL With backpanel cover Without backpanel cover ④ ⑩ RS232 communication port and contacts Input switch ⑤ ⑪ USB communication port Cover for terminals ⑥ ⑫ Slot for optional communication card Terminals for I/O cable connection (refer to related section) ⑦...
3.Installation 3.1 Unpacking 1. Cut the straps and carefully remove the cardboard box by sliding it upwards. 4. Open the protective bag and pull it all the way down. 2. Remove the accessory box, the wooden slide and the 5. Put the previously removed slide on the back part of the top polystyrene foam corner pieces.
3.3 Connection 3.3.1 I NSTALLATION REQUIREMENTS Warning: Installation must be performed by qualified personnel. The first connection to perform is the protective conductor (earth cable), which must be connected to the screw marketed The UPS, when inserted in an installation, does not alter the existing neutral (system earthing) arrangements. A differential switch upstream will also be triggered for a fault occurring downstream of the UPS.
(9E6K INGLE PHASE VERSION I ONLY 4. (SINGLE-PHASE CONNECTION 9E6KI): use 3 cables with cross-section 6 mm (EARTH, N and L) for the input, and 3 cables with cross-section 6 mm for the output (EARTH, N and L). 5. Connect the wires to the relative terminals, following exactly the instructions given below: Input line a - Make sure that the magneto-thermal switch upstream is open.
Page 12
OMBO VERSION INGLE PHASE CONNECTION 4. (SINGLE-PHASE CONNECTION 9E10KI, 9E10KIXL): use 3 cables of cross-section 10 mm (EARTH, N and L) for the input, and 3 cables of cross-section 10 mm for the output(EARTH, N and L). (SINGLE-PHASE CONNECTION 9E15KI, 9E15KIXL): use 3 cables of cross-section 16 mm (EARTH, N and L) for the input, and 3 cables of cross-section 16 mm for the output(EARTH, N and L).
HREE PHASE CONNECTION 1. (THREE-PHASE CONNECTION 9E10KI, 9E10KIXL): Use 2 cables of cross-section 4 mm (L2 and L3) and 3 with cross- section 10 mm (EARTH, N, L1) for the input (N.B.: L1 and N are of greater cross-section because in bypass operation they have to carry all of the input current).
Page 14
2. Insert the screw driver in the square hole and press down to make the round hole terminal open. Then insert the wire into the round hole. Then pull out the screw driver. Connect the two wires of the cable to terminals 5 and 6 (for version 9E6Ki), 7 and 8 (for versions 9E10Ki, 9E10KiXL, 9E15Ki, 9E15KiXL, 9E20Ki, 9E20KiXL) to be able to remotely shut off the UPS.
Page 15
Connect the negative (-) branch wire to EBM’s negative (-) terminal. (Detailed wiring diagram see fig 3-9~10) The suggested tighten force is 1.6Nm. Fig.3-8 EBM terminal view (Fuse for 9E6Ki, 9E10Ki, 9E10KiXLwithout Neutral) Versions 9E6Ki, 9E10Ki, 9E10KiXL Fig.3-9 EBM terminal connection for 9E6Ki, Fig.3-10 EBM terminal connection for 9E6Ki,...
4.OPERATION 4.1 Display and Buttons Fig. 4-1 Control Panel The following tables shows the buttons, LCD indicator and LED indicator status and description: Table 4-1 Control Buttons Functions The Button Function Illustration If the UPS is in standby or bypass mode, press >2s, the buzzer will beep once, then the UPS Turn on system will be turned on.
Page 17
Table 4-3 Buzzer Priority UPS condition Buzzer UPS fault and failure Continuous Normal mode No beep Battery/battery test mode One beep per 4 sec (One beep per 1s when battery low) Bypass mode One beep per 2 minutes Overload One beep per 500ms Other alarm One beep per 1s Manual bypass...
4.2 Operating UPS Notice: Please switch off the connected loads first before turning on the UPS, and switch on the loads one by one after the UPS is turned on. Switch off all of the connected loads before turning off the UPS. Notice: Power on for the first time 1.
It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the 9E UPS battery power becomes low, Eaton Software suite can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
4.4 Trouble shooting PROBLEM POSSIBLE CAUSE SOLUTION Close the input switch located on the back of the INPUT SWITCH OPEN UPS. MAIN CONNECTION CABLE Check that the power cable is connected correctly. MISSING THE DISPLAY DOES NO MAINS VOLTAGE NOT LIGHT UP Check that the power reaches the UPS (BLACKOUT) Reset the thermal protection.
4.5 Alarm codes Using a sophisticated self-diagnosis system, the UPS is able to check its own status and any anomalies and/or faults which may occur during normal operation and display them on the display panel. If there is a problem, the UPS signals the event by showing the code and the type of active alarm on the display.