Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
b.
c.
d.
3.
Record the check results and any corrective actions in a service log.
Figure 41. Air filter location
1
Air filter
8.2.3
Inspect the UPS periodically to determine if components, wiring, and
connections exhibit evidence of overheating. Pay particular attention to bolted
connections. Bolted connections must be re-torqued periodically.
8.2.4
Only authorized personnel that are familiar with the maintenance and
servicing of the UPS system are allowed to perform annual preventive
©
Eaton Corporation plc 2019. All rights reserved.
Remove the upper and lower foam filters from the frame on the front
door.
Install the washed or new foam filters into the frame on the front door.
Close the UPS front door and secure the latch.
Periodic maintenance
Annual maintenance
WARNING
Revision: 002
Document ID: P-164000848
User's and installation guide
104 (118)