Eaton 93E G2 100/100 User And Installation Manual page 70

Table of Contents

Advertisement

Eaton 93E Generation 2 UPS 100-200 kVA
(380/400/415V)
remote EPO switch for this function. Make sure that the wiring of the
remote EPO switch is in accordance with local regulations.
Table 17: Normally-open remote EPO wire connections
From remote EPO
station(s) switch
contact block
(either contact)
3 N.O. 3
4 N.O. 4
Figure 29. Normally-open remote EPO switch wiring
A
B
Table 18: Normally-closed remote EPO wire connections
From remote EPO
station(s) switch
contact block
(either contact)
1 N.C. 1
2 N.C. 2
©
Eaton Corporation plc 2019. All rights reserved.
To remote EPO
terminal block
on the back of UPS
cabinet
See Figure
wiring
Remote EPO switch (N.O.)
Twisted wires
To remote EPO
terminal block
on the back of UPS
cabinet
See Figure
wiring
Wire size
29
for
Twisted wires (2)
(0.5 -2.0 mm
C
UPS Remote EPO terminal (REPO)
Wire size
30
for
Twisted wires (2)
(0.5 -2.0 mm
Revision: 002
Document ID: P-164000848
User's and installation guide
Tightening torque
0.8 Nm
2
)
Tightening torque
0.8 Nm
2
)
70 (118)

Advertisement

Table of Contents
loading

This manual is also suitable for:

93e g2 120/12093e g2 200/16093e g2 200/200

Table of Contents